1SDA068058R1-ABB

XT3N 250 TMD 200-2000 3p F F

C.BREAKER TMAX XT3N 250 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 200-2000 A

In Stock: 11 Available For Shipping

description

Extended Product Type:XT3N 250 TMD 200-2000 3p F F

1SDA068058R1

EAN:8015644019297

Catalog Description:

XT3N 250 TMD 200-2000 3p F F

Long Description:

C.BREAKER TMAX XT3N 250 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 200-2000 A

Quantity
  • Additional Description

    ABB EcoSolutions

    ABB EcoSolutions: Yes

    Circular Value

    Circular Design Principles Recyclability Rate: Design for Closing Resource Loops - Standard EN45555 - 56.6 %

    Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658

    End of Life Instructions:9AKK108468A2350

    Group Waste to Landfill Target:UL 2799 Zero Waste To Landfill Validation available

    Toxic Substances Control Act - TSCA:9AKK108467A8326

    Eco Transparency

    Environmental Product Declaration - EPD:

    9AKK108468A2294

    9AKK108468A7794

    Environmental

    Environmental Information: 9AKK108467A6707

    REACH Declaration: 9AKK108466A1425

    RoHS Information: 9AKK108466A1424

    RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

    SCIP: c29a751a-be17-4df0-832b-bc41e0056527 Italy (IT)

    Simplified SCIP:

    2a076d25-5885-439c-a2e6-562a12b90198 Germany (DE)

    a16b56d1-dc99-4c55-991d-e62075649be4 Poland (PL)

    dfa380c0-88d1-44e8-af7c-e93b491cd27e Netherlands (NL)

    000182ba-09df-4f4a-98fe-0e65e416447e Estonia (EE)

    d7fb814f-534f-4706-9149-d5b6e015862e Greece (GR)

    a34ffad3-0654-4dbf-9a2f-b75b6deeab05 Portugal (PT)

    9c31c87a-6577-4cf2-bff2-c659d2cf4713 Bulgaria (BG)

    79b8eb5a-a8e6-4b80-8e98-4334c54b8e4c Sweden (SE)

    9daa2fe5-d7c4-47cb-bc82-54a00264a086 Denmark (DK)

    8d27fed3-357b-428d-979b-bd2bc3977046 Poland (PL)

    Ordering

    Order Code US and Canada: XT3NE3200AFF000XXX

    E-Number (Finland): 3641004

    EAN: 8015644019297

    Minimum Order Quantity: 1 piece

    Customs Tariff Number: 85362090

    Dimensions

    Product Net Width:105 mm

    Product Net Height: 150 mm

    Product Net Depth / Length: 70 mm

    Product Net Weight: 1.7 kg

    Container Information

    Package Level 1 Units: box 1 piece

    Package Level 1 Width: 155 mm

    Package Level 1 Height:190 mm

    Package Level 1 Depth / Length: 155 mm

    Package Level 1 Gross Weight:

    1.723 kg

    Package Level 1 EAN: 8015644019297

    Additional Information

    Circuit Breaker Type to be Associated: Power Distribution

    Connecting Capacity Main Circuit:Busbar 85..192 mm²

    Current Type: AC/DC

    Electrical Durability:120 cycles per hour

    8000 cycle

    Mechanical Durability:

    240 cycles per hour

    25000 cycle

    Number of Poles: 3

    Opening Time:

    CB with SOR 15 ms

    CB with UVR 15 ms

    Order Multiple:1 piece

     Power Loss: at Rated Operating Conditions per Pole 13.2 W

    Product Main Type: SACE Tmax XT

    Product Name:

    Moulded Case Circuit Breaker

    Product Type: Automatic Circuit Breaker

    Rated Current (In):200 A

    Rated Frequency (f):50 / 60 Hz

    Rated Voltage (Ur):690 V

    Rated Impulse Withstand Voltage (Uimp):8 kV

    Rated Instantaneous Short-Circuit Current Setting (Ii):2000 A

    Rated Insulation Voltage (Ui):800 V

    Rated Operational Voltage:

    690 V AC

    500 V DC

    Rated Service Short-Circuit Breaking Capacity (Ics):

    (220 V AC) 50 kA

    (230 V AC) 50 kA

    (240 V AC) 50 kA

    (380 V AC) 27 kA

    (415 V AC) 36 kA

    (440 V AC) 19 kA

    (500 V AC) 15 kA

    (525 V AC) 9.75 kA

    (690 V AC) 3.75 kA

    (250 V DC) 2 Poles in Series 36 kA

    Rated Ultimate Short-Circuit Breaking Capacity (Icu):

    (220 V AC) 50 kA

    (230 V AC) 50 kA

    (240 V AC) 50 kA

    (380 V AC) 36 kA

    (415 V AC) 36 kA

    (440 V AC) 36 kA

    (500 V AC) 20 kA

    (525 V AC) 13 kA

    (690 V AC) 5 kA

    (250 V DC) 2 Poles in Series 36 kA

    Rated Uninterrupted Current (Iu):250 A

    Recommended Screw Driver:Main Circuit M8

    Release:TMD

    Release Type:TM

    RoHS Date:NA

    Setting Range:140...200 A

    Short-Circuit Performance Level:N

    Standards:IEC60947-2

    Sub-type:XT3

    Terminal Connection Type:Front

    Terminal Type:Bolt

    Tightening Torque:8 N·m

    Version:F

    CAD Dimensional Drawing:

    1SDH001295R0409

  • Certificates and Declarations

    Certificates 

    ATEX Certificate:No certification needed

    Data Sheet, Technical Information:

    1SDC210100D0206

    1SDC210099D0206

    Declaration of Conformity - CE:

    9AKK106713A5530

    GL Certificate:1SDL000163R0094

    LR Certificate:1SDL000163R0100

    UL Certificate:No certification needed

    VDE Certificate:No certification needed

    Dimension Diagram:1SDH000720R0100

    Mechanical Drawings:1SDH000720R0100

    Wiring Diagram:1SDM000068R0001

    Instructions and Manuals:1SDH000720R0001

    Classifications

    ETIM 7: EC000228 - Power circuit-breaker for trafo/generator/installation protection

    ETIM 8:EC000228 - Power circuit-breaker for trafo/generator/installation protection

    ETIM 9: EC000228 - Power circuit-breaker for trafo/generator/installation protection

    Object Classification Code:Q

    UNSPSC: 39120000

    WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)

    eClass: V11.1 : 27370409