1SDA070951R1
1SDA070951R1 - abb
E2.2N 1250 Ekip Dip LI 3p F HR
stock : avialable
General Information
Extended Product Type:
E2.2N 1250 Ekip Dip LI 3p F HR
Product ID:1SDA070951R1
EAN:8015644748012
Catalog Description:
E2.2N 1250 Ekip Dip LI 3p F HR
Long Description:
C.BREAKER SACE EMAX2 E2.2N 1250 FIXED THREE-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/DIP-LI R 1250 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
Specifications Main
ABB EcoSolutions
ABB EcoSolutions:
Yes
Circular Value
Circular Design Principles Recyclability Rate:
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Conflict Minerals Reporting Template (CMRT):
9AKK108467A5658
End of Life Instructions:
9AKK108468A2361
Group Waste to Landfill Target:
UL 2799 Zero Waste To Landfill Validation available
Toxic Substances Control Act - TSCA:
9AKK108467A8326
Eco Transparency
Environmental Product Declaration - EPD:
9AKK108468A1902
9AKK108468A1909
Environmental
Environmental Information:
9AKK108467A6707
REACH Declaration:
9AKK108466A1425
RoHS Information:
9AKK108466A1424
RoHS Status:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP:
5db9272f-d385-4a4a-a0e6-73274e7613b2 Italy (IT)
Ordering
Order Code US and Canada:
Z2NREHBA000A000000XX
EAN:8015644748012
Minimum Order Quantity:
1 piece
Customs Tariff Number:85362090
Dimensions
Product Net Width:276 mm
Product Net Height:371 mm
Product Net Depth / Length:
270 mm
Product Net Weight:41 kg
Container Information
Package Level 1 Units:box 1 piece
Package Level 1 Width:515 mm
Package Level 1 Height:610 mm
Package Level 1 Depth / Length:515 mm
Package Level 1 Gross Weight:46 kg
Package Level 1 EAN:8015644748012
Additional Information
Additional Information
Current Type:AC
Electrical Durability:
Ue =< 440 V 15000 cycle
Ue = 500 ... 690 V 15000 cycle
30 cycles per hour
Mechanical Durability:
25000 cycle
60 cycles per hour
Number of Poles:3
Power Loss:83 W
Product Main Type:SACE Emax 2
Product Name:Air Circuit Breaker
Product Type:Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics):
100 %
Rated Current (In):1250 A
Rated Voltage (Ur):690 V
Rated Impulse Withstand Voltage (Uimp):
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui):AC 1000 V
Rated Operational Voltage:690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics):
(220 V AC) 66 kA
(230 V AC) 66 kA
(380 V AC) 66 kA
(400 V AC) 66 kA
(415 V AC) 66 kA
(440 V AC) 66 kA
(500 V AC) 66 kA
(660 V AC) 66 kA
(690 V AC) 66 kA
Rated Short-time Withstand Current Low Voltage (Icw):
for 1 s 66 kA
for 3 s 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(400 V AC) 66 kA
(415 V AC) 66 kA
(440 V AC) 66 kA
(500 V AC) 66 kA
(525 V AC) 66 kA
(690 V AC) 66 kA
Rated Uninterrupted Current (Iu):1250 A
Recommended Screw Driver:Main Circuit M12
Release:
Ekip Dip LI
Release Type:EL
Short-Circuit Performance Level:N
Standards:IEC
Sub-type:E2.2
Terminal Connection Type:
Rear flat Horizontal
Terminal Type:Bolt
Tightening Torque:70 N·m
Version:F
CAD Dimensional Drawing:
1SDH001252R0083
Certificates and Declarations
ATEX Certificate:
No certification needed
CSA Certificate:
No certification needed
CSA Certificate (Intrinsic Safe):
No certification needed
Data Sheet, Technical Information:1SDC200023D0209
Declaration of Conformity - CE:9AKK106713A5902
UL Certificate:No certification needed
VDE Certificate:No certification needed
Mechanical Drawings:1SDH001000R0100
Wiring Diagram:1SDM000091R0001
Instructions and Manuals:1SDH001000R0002
Classifications
ETIM 7:EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8:EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9:EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC):
4926 >> Air circuit breakers
Object Classification Code:Q
UNSPSC:39121615
WEEE Category:5. Small Equipment (No External Dimension More Than 50 cm)
eClass:
V11.1 : 27370409