1SFL447001R1311
AF140-30-11-13
General Information
Extended Product Type:
AF140-30-11-13
Product ID:
1SFL447001R1311
EAN:
7320500476949
Catalog Description:
AF140-30-11-13 Contactor
Long Description:
The AF140-30-11-13 is a 3 pole - 690 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and double clamp, controlling motors up to 75 kW / 400 V AC (AC-3) or 100 hp / 480 V UL and switching power circuits up to 200 A (AC-1) or 200 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Popular Downloads
Data Sheet, Technical Information:
1SBC100192C0206
Instructions and Manuals:
1SFC100003M0201
CAD Dimensional Drawing:
2CDC001079B0201
Dimension Diagram:
1SFB535001G1051
Dimensions
Product Net Width:
90 mm
Product Net Depth / Length:
126 mm
Product Net Height:
150 mm
Product Net Weight:
1.55 kg
Technical
Number of Main Contacts NO:
3
Number of Main Contacts NC:
0
Number of Auxiliary Contacts NO:
1
Number of Auxiliary Contacts NC:
1
Rated Operational Voltage:
Main Circuit 690 V
Rated Frequency (f):
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 200 A
Rated Operational Current AC-1 (Ie):
(690 V) 40 °C 200 A
(690 V) 70 °C 160 ARated Operational Current AC-3 (Ie):
(415 V) 55 °C 140 A
(440 V) 55 °C 140 A
(500 V) 55 °C 130 A
(690 V) 55 °C 80 A
(380 / 400 V) 55 °C 140 A
(220 / 230 / 240 V) 55 °C 140Rated Operational Current AC-3e (Ie):
(415 V) 60 °C 140 A
(440 V) 60 °C 140 A
(500 V) 60 °C 130 A
(690 V) 60 °C 80 A
(380 / 400 V) 60 °C 140 A
(220 / 230 / 240 V) 60 °C 140 ARated Operational Power AC-3 (Pe):
(415 V) 75 kW
(440 V) 90 kW
(500 V) 90 kW
(690 V) 75 kW
(380 / 400 V) 75 kW
(220 / 230 / 240 V) 37 kWRated Operational Power AC-3e (Pe):
(415 V) 75 kW
(440 V) 90 kW
(500 V) 90 kW
(690 V) 75 kW
(380 / 400 V) 75 kW
(220 / 230 / 240 V) 37 kWRated Breaking Capacity AC-3:
8 x Ie AC-3
Rated Breaking Capacity AC-3e:
8.5 x Ie AC-3e
Rated Making Capacity AC-3:
10 x Ie AC-3
Rated Making Capacity AC-3e:
12 x Ie AC-3e
Short-Circuit Protective Devices:
gG Type Fuses 315 A
Rated Short-time Withstand Current Low Voltage (Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 AMaximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 AMaximum Electrical Switching Frequency:
(AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hourRated Operational Current DC-1 (Ie):
(110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 ARated Operational Current DC-3 (Ie):
(110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 ARated Operational Current DC-5 (Ie):
(110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 ARated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V