top of page
1SFL447101R1311

1SFL447101R1311

SKU: TR
$224.15Price

AF140-40-11-13

General Information

  • Extended Product Type:

    AF140-40-11-13

  • Product ID:

    1SFL447101R1311

  • EAN:

    7320500503744

  • Catalog Description:

    AF140-40-11-13 Contactor

  • Long Description:

    The AF140-40-11-13 is a 4 pole - 690 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and double clamp, controlling motors up to 75 kW / 400 V AC (AC-3) / and switching power circuits up to 200 A (AC-1) or 175 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

  • Ordering

  • Minimum Order Quantity:

    1 piece

  • Customs Tariff Number:

    85364900

  • Popular Downloads

  • Data Sheet, Technical Information:

    1SBC100192C0206

  • Instructions and Manuals:

    1SFC101065M0201

  • CAD Dimensional Drawing:

    2CDC001079B0201

  • Dimension Diagram:

    1SFB535001G1121

  • Product Net Width:

    120 mm

  • Product Net Depth / Length:

    128 mm

  • Product Net Height:

    150 mm

  • Product Net Weight:

    2.05 kg

  • Technical

  • Number of Main Contacts NO:

    4

  • Number of Main Contacts NC:

    0

  • Number of Auxiliary Contacts NO:

    1

  • Number of Auxiliary Contacts NC:

    1

  • Rated Operational Voltage:

    Main Circuit 690 V

  • Rated Frequency (f):

    Main Circuit 60 Hz

  • Conventional Free-air Thermal Current (Ith):

    acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 200 A

  • Rated Operational Current AC-1 (Ie):

    (690 V) 40 °C 200 A
    (690 V) 60 °C 175 A
    (690 V) 70 °C 160 A

  • Rated Operational Current AC-3 (Ie):

    (415 V) 55 °C 140 A
    (440 V) 55 °C 140 A
    (380 / 400 V) 55 °C 140 A
    (220 / 230 / 240 V) 55 °C 140

  • Rated Operational Power AC-3 (Pe):

    (415 V) 75 kW
    (440 V) 90 kW
    (380 / 400 V) 75 kW
    (220 / 230 / 240 V) 37 kW

  • Rated Breaking Capacity AC-3:

    8 x Ie AC-3

  • Rated Making Capacity AC-3:

    10 x Ie AC-3

  • Short-Circuit Protective Devices:

    gG Type Fuses 250 A

  • Rated Short-time Withstand Current Low Voltage (Icw):

    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A

  • Maximum Breaking Capacity:

    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A

  • Maximum Electrical Switching Frequency:

    (AC-1) 300 cycles per hour

  • Rated Insulation Voltage (Ui):

    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
    acc. to UL/CSA 600 V

  • Rated Impulse Withstand Voltage (Uimp):

    Main Circuit 8 kV

  • Mechanical Durability:

    5 million

  • Maximum Mechanical Switching Frequency:

    300 cycles per hour

  • Coil Operating Limits:

    (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)

  • Rated Control Circuit Voltage (Uc):

    50 Hz 100 ... 250 V
    60 Hz 100 ... 250 V
    DC Operation 100 ... 250 V

  • Coil Consumption:

    Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A
    Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A
    Holding at Max. Rated Control Circuit Voltage DC 3 W
    Pull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A
    Pull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A
    Pull-in at Max. Rated Control Circuit Voltage DC 135 W

  • Operate Time:

    Between Coil De-energization and NO Contact Opening 40 ... 70 ms
    Between Coil Energization and NO Contact Closing 20 ... 55 ms

  • Connecting Capacity Main Circuit:

    Flexible 1 x 10 ... 70 mm²
    Rigid Cu-Cable 1 x 10 ... 95 mm²

  • Connecting Capacity Auxiliary Circuit:

    Flexible with Ferrule 2x 0.75 ... 2.5 mm²
    Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
    Flexible 1x0.75 ... 2.5 mm²
    Solid 2 x 1 ... 4 mm²
    Stranded 2 x 1 .... 4 mm²

  • Degree of Protection:

    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00

  • Terminal Type:

    Double Clamp

  • Technical UL/CSA

  • NEMA Size:

    4

  • Horsepower Rating NEMA:

    (200 V AC) Three Phase 40 Hp
    (230 V AC) Three Phase 50 Hp
    (460 V AC) Three Phase 100 Hp
    (575 V AC) Three Phase 100 Hp

  • Maximum Operating Voltage UL/CSA:

    Main Circuit 600 V

  • General Use Rating UL/CSA:

    (600 V AC) 200 A

  • Horsepower Rating UL/CSA:

    (200 ... 208 V AC) Three Phase 15 Hp
    (200 V AC) Three Phase 40 hp
    (208 V AC) Three Phase 40 hp
    (220 ... 240 V AC) Three Phase 20 Hp
    (220 ... 240 V AC) Three Phase 50 hp
    (440 ... 480 V AC) Three Phase 40 Hp
    (440 ... 480 V AC) Three Phase 100 hp
    (550 ... 600 V AC) Three Phase 50 Hp
    (550 ... 600 V AC) Three Phase 125 hp

  • Dimensions

No Reviews YetShare your thoughts. Be the first to leave a review.