1SFL447101R1311
AF140-40-11-13
General Information
Extended Product Type:
AF140-40-11-13
Product ID:
1SFL447101R1311
EAN:
7320500503744
Catalog Description:
AF140-40-11-13 Contactor
Long Description:
The AF140-40-11-13 is a 4 pole - 690 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and double clamp, controlling motors up to 75 kW / 400 V AC (AC-3) / and switching power circuits up to 200 A (AC-1) or 175 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Ordering
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85364900
Popular Downloads
Data Sheet, Technical Information:
1SBC100192C0206
Instructions and Manuals:
1SFC101065M0201
CAD Dimensional Drawing:
2CDC001079B0201
Dimension Diagram:
1SFB535001G1121
Product Net Width:
120 mm
Product Net Depth / Length:
128 mm
Product Net Height:
150 mm
Product Net Weight:
2.05 kg
Technical
Number of Main Contacts NO:
4
Number of Main Contacts NC:
0
Number of Auxiliary Contacts NO:
1
Number of Auxiliary Contacts NC:
1
Rated Operational Voltage:
Main Circuit 690 V
Rated Frequency (f):
Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 200 A
Rated Operational Current AC-1 (Ie):
(690 V) 40 °C 200 A
(690 V) 60 °C 175 A
(690 V) 70 °C 160 ARated Operational Current AC-3 (Ie):
(415 V) 55 °C 140 A
(440 V) 55 °C 140 A
(380 / 400 V) 55 °C 140 A
(220 / 230 / 240 V) 55 °C 140Rated Operational Power AC-3 (Pe):
(415 V) 75 kW
(440 V) 90 kW
(380 / 400 V) 75 kW
(220 / 230 / 240 V) 37 kWRated Breaking Capacity AC-3:
8 x Ie AC-3
Rated Making Capacity AC-3:
10 x Ie AC-3
Short-Circuit Protective Devices:
gG Type Fuses 250 A
Rated Short-time Withstand Current Low Voltage (Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 AMaximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A
Maximum Electrical Switching Frequency:
(AC-1) 300 cycles per hour
Rated Insulation Voltage (Ui):
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 VRated Impulse Withstand Voltage (Uimp):
Main Circuit 8 kV
Mechanical Durability:
5 million
Maximum Mechanical Switching Frequency:
300 cycles per hour
Coil Operating Limits:
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc):
50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 VCoil Consumption:
Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A
Holding at Max. Rated Control Circuit Voltage DC 3 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 135 WOperate Time:
Between Coil De-energization and NO Contact Opening 40 ... 70 ms
Between Coil Energization and NO Contact Closing 20 ... 55 msConnecting Capacity Main Circuit:
Flexible 1 x 10 ... 70 mm²
Rigid Cu-Cable 1 x 10 ... 95 mm²Connecting Capacity Auxiliary Circuit:
Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 1x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00Terminal Type:
Double Clamp
Technical UL/CSA
NEMA Size:
4
Horsepower Rating NEMA:
(200 V AC) Three Phase 40 Hp
(230 V AC) Three Phase 50 Hp
(460 V AC) Three Phase 100 Hp
(575 V AC) Three Phase 100 HpMaximum Operating Voltage UL/CSA:
Main Circuit 600 V
General Use Rating UL/CSA:
(600 V AC) 200 A
Horsepower Rating UL/CSA:
(200 ... 208 V AC) Three Phase 15 Hp
(200 V AC) Three Phase 40 hp
(208 V AC) Three Phase 40 hp
(220 ... 240 V AC) Three Phase 20 Hp
(220 ... 240 V AC) Three Phase 50 hp
(440 ... 480 V AC) Three Phase 40 Hp
(440 ... 480 V AC) Three Phase 100 hp
(550 ... 600 V AC) Three Phase 50 Hp
(550 ... 600 V AC) Three Phase 125 hpDimensions