1SVR730794R3300-ABB

CM-PVS.41S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x300-500VAC

In Stock: 50

General Information

  • Extended Product Type:

    CM-PVS.41S

  • Product ID: 1SVR730794R3300

  • EAN: 4016779851848

  • Catalog Description:

    CM-PVS.41S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x300-500VAC

  • Long Description:

    The CM-PVS.41S relay is from the CM three-phase monitors range. This relay operates with a rated control supply voltage / three-phase measuring voltage of 300-500 V AC and has a 2 c/o output with contacts rated at 250 V / 4 A. The CM-PVS.41S monitors the phase parameters over/undervoltage and phase failure. The corresponding threshold values are adjustable. Phase sequence monitoring as well as an ON or OFF tripping delay are selectable. The tripping delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.

  • Dimensions

    • Product Net Width: 22.5 mm

    • Product Net Height: 85.6 mm

    • Product Net Depth / Length: 103.7 mm

    • Product Net Weight: 0.139 kg

  • Technical

    Function:

    Phase failure detection

    Phase sequence monitoring

    Over- and undervoltage monitoring

    Measuring Range: (L-L) 300 ... 500 V AC

    Time Range:

    200 ms start-up delay

    0 s or 0.1 ... 30 s tripping delay (ON or OFF)

    Rated Control Supply Voltage (Us): (L-L) 300 ... 500 V AC

    Rated Frequency (f): Supply Circuit 50/60 Hz

    Output: 2 c/o (SPDT) contacts

    Terminal Type: Screw Terminals

    Rated Operational Current AC-12 (Ie): (230 V) 4 A

    Rated Operational Current AC-15 (Ie): (230 V) 3 A

    Rated Operational Current DC-12 (Ie): (24 V) 4 A

    Rated Operational Current DC-13 (Ie): (24 V) 2 A

    Minimum Switching Capacity:

    24 V

    10 mA

    Rated Impulse Withstand Voltage (Uimp):

    Input Circuit 6 kV

    Output Circuit 4 kV

    Rated Insulation Voltage (Ui):

    Input Circuit / Output Circuit 600 V

    Output Circuit 1 / Output Circuit 2 300 V

    Degree of Protection:

    Housing IP50

    Terminals IP20

    Overvoltage Category: III

    Pollution Degree: 3

    Short-Circuit Protective Devices:

    Output Circuit NC - F Type Fuses 6 A

    Output Circuit NO - F Type Fuses 10 A

    Electrical Durability: AC-12 100000 cycle

    Mechanical Durability:

    30000000 cycle