top of page
1SVR730830R0500

1SVR730830R0500

SKU: 101
$154.00 Regular Price
$138.60Sale Price

1SVR730830R0500-ABB

CM-ESS.MS Voltage monitoring relay 2c/o, B-C=3-600VRMS, 24-240VAC/DC
In Stock: 70

General Information

  • Extended Product Type:

  • CM-ESS.MS

  • Product ID: 1SVR730830R0500

  • EAN: 4016779852173

  • Catalog Description:

    CM-ESS.MS Voltage monitoring relay 2c/o, B-C=3-600VRMS, 24-240VAC/DC

  • Long Description:

    The CM-ESS.MS is a multifunctional voltage monitoring relay from the CM single-phase monitors range. This monitoring relay operates with a rated control supply voltage of 24 - 240 V AC / DC and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. It provides a RMS measuring principle for DC and AC voltages with 4 measuring ranges: 3-30 V, 6-60 V, 30-300 V and 60-600 V. The CM-ESS.MS offers selection of over- or undervoltage monitoring, open- or closed-circuit operating principle, with or without latching function. The hysteresis is adjustable within a range of 3 to 30 % of the threshold value. The tripping delay and the start-up delay are adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.

Quantity
  • Addisional Information

    Dimensions

    Product Net Width:

    22.5 mm

    Product Net Height:

    85.6 mm

    Product Net Depth / Length:

    103.7 mm

    Product Net Weight:

    0.154 kg

  • Addisional Information

    Technical

    Function:

    Over- or undervoltage monitoring

    Measuring Range:

    3 ... 30 V

    6 ... 60 V

    30 ... 300 V

    60 ... 600 V

    Time Range:

    0 s or 0.1 ... 30 s tripping delay (ON)

    Rated Control Supply Voltage (Us):

    24 ... 240 V AC/DC

    Output:

    2 c/o (SPDT) contact; operating principle selectable

    Terminal Type:

    Screw Terminals

    Rated Operational Current AC-12 (Ie):

    (230 V) 4 A

    Rated Operational Current AC-15 (Ie):

    (230 V) 3 A

    Rated Operational Current DC-12 (Ie):

    (24 V) 4 A

    Rated Operational Current DC-13 (Ie):

    (24 V) 2 A

    Minimum Switching Capacity:

    24 V

    10 mA

    Rated Impulse Withstand Voltage (Uimp):

    Measuring Circuit / Output Circuit 6 kV

    Output Circuit 1 / Output Circuit 2 4 kV

    Supply Circuit / Measuring Circuit 6 kV

    Supply Circuit / Output Circuit 4 kV

    Rated Insulation Voltage (Ui):

    Measuring Circuit / Output Circuit 600 V

    Output Circuit 1 / Output Circuit 2 250 V

    Supply Circuit / Measuring Circuit 600 V

    Supply Circuit / Output Circuit 250 V

    Degree of Protection:

    Housing IP50

    Terminals IP20

    Overvoltage Category:

    III

    Pollution Degree:

    3

    Short-Circuit Protective Devices:

    Output Circuit NC - F Type Fuses 10 A

    Output Circuit NO - F Type Fuses 10 A

    Electrical Durability:

    AC-12 100000 cycle

    Mechanical Durability:

    30000000 cycle

    Connecting Capacity:

    Flexible with Ferrule 1x 0.5 ... 2.5 mm²

    Flexible with Ferrule 2x 0.5 ... 1.5 mm²

    Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm²

    Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²

    Flexible 1x 0.5 ... 2.5 mm²

    Flexible 2x 0.5 ... 1.5 mm²

    Rigid 1x 0.5 ... 4 mm²

    Rigid 2x 0.5 ... 2.5 mm²

    Tightening Torque:

    0.6 ... 0.8 N·m

    Wire Stripping Length:

    8 mm

    Recommended Screw Driver:

    0.8 x 4

    4.5

    Pozidriv 1

    Mounting Position:

    1 ... 6

    Mounting on DIN Rail:

    TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715

    TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715

    Standards:

    CAN/CSA C22.2 No.14

    IEC/EN 63000

    IEC/EN 60255-27

    IEC/EN 61000-6-2

    IEC/EN 61000-6-3

    UL 508

No Reviews YetShare your thoughts. Be the first to leave a review.