2CDS252001R0254
General Information
Extended Product Type:
S202-C25
Product ID:
2CDS252001R0254
EAN:
4016779466103
Catalog Description:
S202-C25 Miniature Circuit Breaker - 2P - C - 25 A
Long Description:
System pro M compact S200 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200 comply with IEC/EN 60898-1, IEC/EN 60947-2, UL1077 allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200 to save 50% space.
Technical
Standards:
IEC/EN 60898-1
IEC/EN 60947-2
UL 1077Tripping Characteristic:
C
Rated Operational Voltage:
acc. to IEC 60898-1 400 V AC
acc. to IEC 60898-1 400 V
acc. to IEC 60947-2 440 V ACOperational Voltage:
Maximum (Incl. Tolerance) 125 V DC
Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC
Minimum 12 V DCEnvironmental
Ambient Air Temperature:
Operation -25 ... +55 °C
Storage -40 ... +70 °CReference Ambient Air Temperature:
30 °C
Degree of Protection:
IP20
IP40
Enclosure with Cover IP40Pollution Degree:
3
Environmental Conditions:
28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %Resistance to Vibrations acc. to IEC 60068-2-6:
5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
Resistance to Shock acc. to IEC 60068-2-27:
25g 2 shocks 13 ms
RoHS Status:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
RoHS Information:
2CDK403001D0607
REACH Declaration:
9AKK107492A1906
SCIP:
e6800e55-46b1-49a3-881b-0f66d0e903ad Germany (DE)
Conflict Minerals Reporting Template (CMRT):
9AKK108468A3363
Technical UL/CSA
Maximum Operating Voltage UL/CSA:
110 V DC
480Y/277 V ACInterrupting Rating acc. to UL1077:
(277 V AC) 6 kA
(480Y / 277 V AC) 6 kA
(240 V) 10 kAConnecting Capacity UL/CSA:
Busbar 18-8 AWG
Conductor 18-4 AWGTightening Torque UL/CSA:
18 in·lb
Rated Insulation Voltage (Ui):
acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp):
4 kV
at 2000 m 5 kV
at Sea Level 6.2 kVDielectric Test Voltage:
50/60 Hz, 1 min: 2 kV
Input Voltage Type:
AC/DC
Rated Current (In):
25 A
Rated Short-Circuit Capacity:
(AC) 6 kA
(DC) 6 kA
(400 V AC) 6 kA