top of page
2CDS252001R0254

2CDS252001R0254

SKU: TR
$9.53Price

General Information

  • Extended Product Type:

    S202-C25

  • Product ID:

    2CDS252001R0254

  • EAN:

    4016779466103

  • Catalog Description:

    S202-C25 Miniature Circuit Breaker - 2P - C - 25 A

  • Long Description:

    System pro M compact S200 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200 comply with IEC/EN 60898-1, IEC/EN 60947-2, UL1077 allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200 to save 50% space.

  • Technical

  • Standards:

    IEC/EN 60898-1
    IEC/EN 60947-2
    UL 1077

  • Tripping Characteristic:

    C

  • Rated Operational Voltage:

    acc. to IEC 60898-1 400 V AC
    acc. to IEC 60898-1 400 V
    acc. to IEC 60947-2 440 V AC

  • Operational Voltage:

    Maximum (Incl. Tolerance) 125 V DC
    Maximum (Incl. Tolerance) 440 V AC
    Minimum 12 V AC
    Minimum 12 V DC

  • Environmental

  • Ambient Air Temperature:

    Operation -25 ... +55 °C
    Storage -40 ... +70 °C

  • Reference Ambient Air Temperature:

    30 °C

  • Degree of Protection:

    IP20
    IP40
    Enclosure with Cover IP40

  • Pollution Degree:

    3

  • Environmental Conditions:

    28 cycles
    with 55 °C / 90-96 %
    and 25 °C / 95-100 %

  • Resistance to Vibrations acc. to IEC 60068-2-6:

    5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In

  • Resistance to Shock acc. to IEC 60068-2-27:

    25g 2 shocks 13 ms

  • RoHS Status:

    Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

  • RoHS Information:

    2CDK403001D0607

  • REACH Declaration:

    9AKK107492A1906

  • SCIP:

    e6800e55-46b1-49a3-881b-0f66d0e903ad Germany (DE)

  • Conflict Minerals Reporting Template (CMRT):

    9AKK108468A3363

  • Technical UL/CSA

  • Maximum Operating Voltage UL/CSA:

    110 V DC
    480Y/277 V AC

  • Interrupting Rating acc. to UL1077:

    (277 V AC) 6 kA
    (480Y / 277 V AC) 6 kA
    (240 V) 10 kA

  • Connecting Capacity UL/CSA:

    Busbar 18-8 AWG
    Conductor 18-4 AWG

  • Tightening Torque UL/CSA:

    18 in·lb

  •  
  • Rated Insulation Voltage (Ui):

    acc. to IEC/EN 60664-1 440 V

  • Rated Impulse Withstand Voltage (Uimp):

    4 kV
    at 2000 m 5 kV
    at Sea Level 6.2 kV

  • Dielectric Test Voltage:

    50/60 Hz, 1 min: 2 kV

  • Input Voltage Type:

    AC/DC

  • Rated Current (In):

    25 A

  • Rated Short-Circuit Capacity:

    (AC) 6 kA
    (DC) 6 kA
    (400 V AC) 6 kA