General Information

  • Extended Product Type:

    S201M-C2

  • Product ID:

    2CDS271001R0024

  • EAN:

    4016779549936

  • Catalog Description:

    S201M-C2 Miniature Circuit Breaker - 1P - C - 2 A

  • Long Description:

    System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.

  • Circular Value

  • Circular Design Principles Recyclability Rate:

    Design for Closing Resource Loops - Standard EN45555 - 90 %

  • Sustainable Material Content:

    0 %

  • Offered with Extended Lifetime:

    Product Durability

  • Offered with Takeback Services:

    Take Back for Recycling

  • Eco Transparency

  • Environmental Product Declaration - EPD:

    9AKK108467A7833

  • Technical

  • Standards:

    IEC/EN 60898-1
    CSA 22.2 No. 235
    IEC/EN 60947-2
    UL 1077

  • Tripping Characteristic:

    C

  • Rated Operational Voltage:

    acc. to IEC 60898-1 230 / 400 V AC
    acc. to IEC 60898-1 230 V
    acc. to IEC 60947-2 230 V AC

  • Environmental

  • Ambient Air Temperature:

    Operation -25 ... +55 °C
    Storage -40 ... +70 °C

  • Reference Ambient Air Temperature:

    30 °C

  • Degree of Protection:

    IP20
    IP40
    Enclosure with Cover IP40

  • Pollution Degree:

    3

  • Environmental Conditions:

    28 cycles
    with 55 °C / 90-96 %
    and 25 °C / 95-100 %

  • Resistance to Vibrations acc. to IEC 60068-2-6:

    5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In

  • Resistance to Shock acc. to IEC 60068-2-27:

    25g 2 shocks 13 ms

  • RoHS Status:

    Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

  • RoHS Information:

    2CDK400003K0203

  • REACH Declaration:

    9AKK107492A1906

  • SCIP:

    9008497a-14f6-4cfd-83c5-11cf3bc660d1 Germany (DE)

  • Conflict Minerals Reporting Template (CMRT):

    9AKK108468A3363

  • Technical UL/CSA

  • Maximum Operating Voltage UL/CSA:

    60 V DC
    480Y/277 V AC

  • Interrupting Rating acc. to UL1077:

    (277 V AC) 6 kA
    (480Y / 277 V AC) 6 kA
    (60 V DC) 10 kA

  • Connecting Capacity UL/CSA:

    Busbar 14-8 AWG
    Conductor 14-4 AWG

  • Tightening Torque UL/CSA:

    18 in·lb

  • Dimensions

  • Width in Number of Modular Spacings:

    1

  • Product Net Width:

    17.5 mm

  • Product Net Height:

    88 mm

  • Product Net Depth / Length:

    69 mm

  • Product Net Weight:

    0.125 kg

  • Pole Net Weight:

    0.125 kg

  • Built-In Depth (t2):

    69 mm

  • Dimension Diagram:

    2CDC022007F0010

  •  
  • Operational Voltage:

    Maximum (Incl. Tolerance) 253 V AC
    Maximum (Incl. Tolerance) 72 V DC
    Minimum 12 V AC
    Minimum 12 V DC

  • Rated Insulation Voltage (Ui):

    acc. to IEC/EN 60664-1 440 V

  • Rated Impulse Withstand Voltage (Uimp):

    4 kV
    at 2000 m 5 kV
    at Sea Level 6.2 kV

  • Dielectric Test Voltage:

    50/60 Hz, 1 min: 2 kV

  • Input Voltage Type:

    AC/DC

  • Rated Current (In):

    2 A

  • Rated Short-Circuit Capacity:

    (AC) 10 kA
    (230 / 400 V AC) 10 kA
    (230 V) 10 kA
    (400 V) 10 kA

  • Rated Ultimate Short-Circuit Breaking Capacity (Icu):

    (133 V AC) 25 kA
    (230 V AC) 15 kA
    (230 V) 15 kA
    (400 V) 15 kA

  • Rated Conditional Short-Circuit Current (Inc):

    (230 V) 15 kA

  • Rated Service Short-Circuit Breaking Capacity (Ics):

    (133 V AC) 18.8 kA
    (230 V AC) 7.5 kA

  • Frequency (f):

    50 Hz

  • Rated Frequency (f):

    50 / 60 Hz
    50 ... 60 Hz

  • Power Loss:

    1.8 W
    at Rated Operating Conditions per Pole 1.8 W

  • Power Supply Connection:

    Arbitrary

  • Contact Position Indication:

    Red ON / Green OFF

  • Energy Limiting Class:

    3

  • Electrical Endurance:

    20000 AC cycle

  • Mechanical Endurance:

    20000 cycle

  • Number of Poles:

    1

  • Number of Protected Poles:

    1

  • Overvoltage Category:

    III

  • Tightening Torque:

    2.8 N·m

  • Screw Terminal Type:

    Failsafe Bi-directional Cylinder-lift Terminal

  • Actuator Marking:

    I / O

  • Actuator Material:

    Insulation Group II, Black, Sealable

  • Housing Material:

    Insulation Group II, RAL 7035

  • Mounting on DIN Rail:

    TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
    TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715

  • Mounting Position:

    any

  • Recommended Screw Driver:

    Pozidriv 2

  • Accessories Available:

    Yes

  • Connecting Capacity:

    Busbar 10 / 10 mm²
    Flexible with Ferrule 0.75 ... 25 mm²
    Flexible 0.75 ... 25 mm²
    Flexible 0.75 ... 25 mm²
    Rigid 0.75 ... 35 mm²
    Rigid 0.75 ... 35 mm²
    Stranded 0.75 ... 35 mm²

  • Installation Size:

    acc. to DIN 43880 1

  • Terminal Type:

    Screw Terminals

No Reviews YetShare your thoughts. Be the first to leave a review.