2CSR255080R1064
2CSR255080R1064 - ABB
Extended Product Type: DS201 C6 AC30
DS201 C6 AC30 Residual Current Circuit Breaker with Overcurrent Protection
In Stock
Description:
The DS201 series is a 1P+N RCBO in two-modules width for the protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct contacts.
Dimensions
Width in Number of Modular Spacings: 2
Product Net Width: 0.035 m
Product Net Height: 0.085 m
Product Net Depth / Length: 0.069 m
Product Net Weight: 0.200 kg
Built-In Depth (t2): 69 mm
Environmental
Ambient Temperature:
-25...55 °C
Ambient Air Temperature:
Operation -25 … 55 °C
Reference Ambient Air Temperature:
30 °C
Degree of Protection:
IP20
IP40
Pollution Degree:
2
Environmental Conditions:
28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Resistance to Vibrations:
20 Cycles with Load 0.8 In: 1g or 1mm 50 … 150 … 5 Hz
Resistance to Shock acc. to IEC 60068-2-27:
25g 2 shocks 13 ms
Classifications
ETIM 8: 000905 - Earth leakage circuit breaker
ETIM 9:
EC000905 - Earth leakage circuit breaker
WEEE Category:
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B: Business To Consumer
CN8: 85363010
eClass: V11.0 : 27142207
Object Classification Code: F
TECHNICAL INFORMATION
Standards:
IEC/EN 61009-1, IEC/EN 61009-2-1
Tripping Characteristic: C
Type of Residual Current:
Type AC
Rated Voltage (Ur):
230 V
Rated Operational Voltage:
acc. to IEC 60898-1 240 V
Rated Insulation Voltage (Ui):
acc. to IEC/EN 60664-1 500 V
Test Voltage (Ut): 170 ... 264 V
Dielectric Test Voltage: 2 kV
Primary Rated Impulse Withstand Voltage: 4 kV
Input Voltage Type: AC
Rated Current (In): 6 A
Rated Residual Current: 30 mA
Rated Short-Circuit Capacity: 6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):10 kA
Addisional Information
Rated Residual Breaking Capacity (IΔm):
EN 61009-1 6000 A
IEC 61009-1 6000 A
Rated Conditional Short-Circuit Current (Inc):
10 kA
Rated Service Short-Circuit Breaking Capacity (Ics):
7.5 kA
Maximum Surge Current:
0 kA
Leakage Current Type:
AC
Frequency (f):
50/60 Hz
Rated Frequency (f):
50 … 60 Hz
Power Loss:
Average per Pole 1.3 W
Phase Pole 2.4 W
Neutral Pole 0.2 W
Total 2.6 W
Power Supply Connection:
Arbitrary
Contact Position Indication:
Red ON / Green OFF
Energy Limiting Class:
3
Electrical Endurance:
10000 cycle
Mechanical Endurance:
20000 cycle
Number of Protected Poles:
1
Number of Poles:
2
Number of Modular Spacings per DIN Rail:
2
Fault Indication:
Blue flag on toggle
Operating Characteristic:
Instantaneous
Overvoltage Category:
III
Position of Neutral Terminals:
Right
Tightening Torque:
2.8 N·m
Accessory Type:
Auxiliary contact, Signal contact / auxiliary contact, Shunt trip, Auxiliary contact for bottom fitting, Overvoltage release, Motor operating device
Actuator Type:
Toggle - Insulation group II, Black RAL 9005, sealable in ON-OFF positions
Housing Type:
Insulation group I - II, RAL 7035
Mounting Type:
DIN-Rail
Release Type:
C
Screw Terminal Type:
Failsafe Bi-directional Cylinder-lift Terminal
Mounting Position:
Any
Accessories Available:
Yes
Number of Batteries:
0
Cable Size:
25 mm²
Connecting Capacity:
Busbar 10 ... 10 mm²
Stranded 0.75 ... 25 mm²
Flexible with Ferrule 0.75 ... 16 mm²
Flexible 0.75 ... 16 mm²
Wire Stripping Length:
12 mm
Terminal Type:
Screw Terminals