A9D31610
A9D31610 - scheinder
Acti 9 iDPN N Vigi - RCBO - 1P+N - 10A - C Curve - 6000A - 30mA - type AC
stock: 49
Description
This Acti9 iDPN Vigi is a modular residual current breaker with overcurrent protection (RCBO). It is a 1P+N circuit breaker with 1 protected pole, 10A In rated current and C tripping curve. The earth leakage protection class is AC type with a sensitivity of 30mA. The earth-leakage protection time delay is instantaneous. The Icn rated short circuit breaking capacity is up to 6000A according EN/IEC 61009-2-1 standard. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. Its earth fault indicator on front face allows quick identification of the type of default. It can be fitted instead of a miniature circuit breaker for complete protection of one circuit. This product is compliant with EN/IEC 61009-2-1 standard. It has an electrical endurance going up to 20000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 220VAC to 240VAC. The Ui rated insulation voltage is 400VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product color is white (RAL9003). The dimensions are (W) 36mm x (H) 85mm x (D) 73mm. The weight is 125g. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. The operating temperature is from -5°C to 60°C. The storage temperature is from -40°C to 85°C.
Specifications Main
Main Range Acti9 Product name Acti9 iDPN Vigi Product or component type Residual current breaker with overcurrent protection (RCBO) Device short name iDPN N Vigi Device application Distribution Poles description 1P + N Number of protected poles 1 Neutral position Left [In] rated current 10 A Network type AC Trip unit technology Thermal-magnetic Curve code C Earth-leakage sensitivity 30 mA Earth-leakage protection time delay Instantaneous Earth-leakage protection class Type AC Breaking capacity 6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 Suitability for isolation Yes conforming to EN/IEC 60947-2 Complementary Complementary Outgoer Network frequency 50 Hz [Ue] rated operational voltage 230...240 V AC 50 Hz Magnetic tripping limit 5...10 x In Residual current tripping technology Voltage independent [Ics] rated service breaking capacity 6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 Rated breaking and making capacity Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 Limitation class 3 conforming to EN/IEC 61009-2-1 [Ui] rated insulation voltage 400 V AC 50 Hz [Uimp] rated impulse withstand voltage 4 kV Contact position indicator Yes Control type Toggle Local signalling ON, OFF, fault trip Mounting mode Clip-on Mounting support DIN rail Comb busbar and distribution block compatibility Top or bottom: YES Connection pitch 9 mm between phase and neutral 9 mm pitches 4 Height 85 mm Width 36 mm Depth 73 mm Net weight 125 g Colour White Mechanical durability 20000 cycles Electrical durability 20000 cycles Locking options description Padlocking device Connections - terminals Single terminal top or bottom 1…16 mm² rigid
Single terminal top or bottom 1…10 mm² flexible
Single terminal top or bottom 1…10 mm² flexible with ferruleWire stripping length 15 mm for top or bottom connection Tightening torque 2 N.m top or bottom Earth-leakage protection Integrated Environment and Packing Units
Environment Standards EN/IEC 61009-2-1 Product certifications VDE
GOSTIP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529Pollution degree 3 Overvoltage category III conforming to IEC 60364 Electromagnetic compatibility 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1 Tropicalisation 2 conforming to IEC 60068-1 Relative humidity 95 % at 55 °C Ambient air temperature for operation -5…60 °C Ambient air temperature for storage -40…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 4.000 cm Package 1 Width 8.500 cm Package 1 Length 10.000 cm Package 1 Weight 207.000 g Unit Type of Package 2 S03 Number of Units in Package 2 54 Package 2 Height 30.000 cm Package 2 Width 30.000 cm Package 2 Length 40.000 cm Package 2 Weight 11.601 kg properties
Protection of persons against electric shock by direct contact
Combine short-circuit and overload currents protection
Suitability for isolation according to IEC 61009-1 and IEC 61009-2-1 standards
Easy to install with unified terminal design and wiring indication
Earth fault indication by a red mechanical indicator in front face
Environmental performance of the product Learn more