A9E16065
A9E16065 - scheinder
iRTA relay - delays the energization of a load - 1C/O - Uc 24-240 VAC/24VDC
stock : 50description
Delays the onset of the load Single time daily cycle starts with the iRTA relay power supply switch ON Control and power supply voltage Uc is between 24VAC and 240VAC +/- 10% and 24VDC +/- 10% The load is energized after the time delay T Operating frequency 50Hz or 60Hz The sensitivity of the device is +/- 10% of full scale Minimum duration of the control pulse 100ms Maximum reset time per voltage interruption 100ms Nominal switching current is 21A at 250VAC Mechanical endurance under category AC1 is above 5 x 10exp6 switching operations Electrical endurance under category AC1 is above 10exp5 in switching operations The device flashes during the time delay Contains a changeover contact Width at 9mm level 2 Degree of protection IP20 Dimensions (W) 18mm x (H) 90mm x (D) 72mm Weight 65g Operating temperature -5°C to +55°C Storage temperature -40°C to +70°C.
Specifications Main
Main
Relay application Time delay relay time delay type Delays in energizing the load sherry Acti9 product name IRT Product group IRTA signal contact arrangement 1 C/A Complement
[Ie] rated operating current 8 A at 250 V AC
8 A at 250 V DC
0.01 A at 5 V DCpulse duration > 100ms local signaling LED, time delay for flashing
LED green for power ONtype of setting Rotary knob: time delay configuration time delay interval 0.1...360000 s truth error +/- 10% repeat accuracy +/- 0.5% control circuit voltage 24...240 V AC 50/60 Hz
24 V DC[Us] nominal supply voltage 24...240 V AC at 50/60 Hz
24 V DCMounting Type Still mounting support 35 mm symmetrical DIN rail 9mm screw pitch 2 Height 93mm Width 18mm Depth 72mm Product weight 0.065 kg Colour White mechanical strength 5000000 cycles electrical resistance AC-1: 100000 cycles undervoltage behavior 100ms connections - terminals For tunnel type terminals 2 cable(s) 1.5 mm² flexible With cable end
For tunnel type terminals 2 cable(s) 1.5 mm² flexible Without cable end
For tunnel type terminals 2 cable(s) 2.5 mm² rigid With cable end
For tunnel type terminals 2 cable(s) 2.5 mm² rigid Without cable endEnvironment and Packing Units
IP protection degree IP20 Immune to microfractures 20ms Nominal operating ambient temperature -5…55 °C Storage environmental conditions -40…70 °C Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 2.4 cm Package 1 Width 7.4 cm Package 1 Length 10.3 cm Package 1 Weight 80g