A9F73206
A9F73206 - schneider
iC60N - miniature circuit breaker - 2P - 6A - B curve
stock: 18description
Rated short-circuit breaking capacity is up to 20kA at 220VAC to 240VAC according to EN/IEC 60947-2 and up to 6000A at 400VAC according to EN/IEC 60898-1 This miniature circuit breaker protects circuits against short-circuit and overload current The unique Visitrip indicator reduces intervention time by indicating the faulty circuit Visisafe green strip ensures physical opening of the contacts to allow downstream maintenance Quick closing mechanism independent of manual operation extends the service life Electrical endurance up to 10000 cycles and mechanical endurance up to 20000 cycles Rated insulation voltage Ui is 500VAC Limitation class 3 (according to EN/IEC60898-1) increases the cost of downstream circuit protection Product Can be clipped to DIN rail Width 9mm at levels 4 Overvoltage category IV Product colour is white (RAL9003) Dimensions (W) 36mm x (H) 85mm x (D) 78.5mm Weight 0.25kg Degree of protection in the box IP20 and IP40 according to IEC Standard 60529 Operating temperature -35°C to 70°C Storage temperature -40°C to 85°C.
Specifications Main
Main
device application Distribution sherry Act 9 product name Acti9 iC60 Product or component type Miniature circuit breaker Product group IC60N Definition of pole 2P number of protected poles 2 [In] nominal current 6 A Network type DC
ACopening unit technology Thermal Magnetic slope code B cutting capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at < = 125 V DC conforming to EN/IEC 60947-2
10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220...240 V AC 50/ 60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2Usage category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for insulation Yes conforming to TR 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2Standards EN 60947-2
IEC 60898-1
TR 60898-1
IEC 60947-2Complement
Network frequency 50/60Hz magnetic opening limit 4 x In +/- 20% [Ics] nominal service interrupting capacity 15 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 - 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz
27 kA 75 % conforming
to IEC 60947-2 - 12...133 V AC 50/60 Hz 27 kA 75 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
6000 A 100 % conforming to TR 60898-1 - 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 - 72...125 V DC
10 kA 100 % conforming to EN 60947-2 - 72...125 V DCrestriction class 3 conforming to TR 60898-1
3 conforming to IEC 60898-1[Ui] nominal insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage Conforming to 6 kV EN 60947-2
Conforming to 6 kV IEC 60947-2ignition position indicator Yes Control type Transition On-device signaling Open indicator Mounting Type Still mounting support DIN rail comb busbar distribution block compatibility Top or bottom: YES 9mm screw pitch 4 Height 85mm Width 36mm Depth 78.5mm Product weight 0.25kg colour White Mechanical durability 20000 cycles electrical resistance 10000 cycles connections - terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connection tightening torque 2 Nm above or below earth leakage protection Separate block Environment and Packing Units
Environment
IP protection degree
IP20 conforming to IEC 60529degree of contamination 3 conforming to EN 60947-2
3 conforming to IEC 60947-2overvoltage category IV tropical climate 2 conforming to IEC 60068-1 relative humidity 95% at 55 °C working height 0...2000m Nominal operating ambient temperature -35…70 °C Storage environmental conditions -40…85 °C Packaging units
Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 3,500 cm Package 1 Width 7,200 cm Package 1 Length 9,200 cm Package 1 Weight 214,000g Unit Type of Package 2 BB1 Number of Units in Package 2 6 Package 2 Height 8,200 cm Package 2 Width 10,000 cm Package 2 Length 22,400 cm Package 2 Weight 1,348 kg Unit Type of Package 3 S03 Number of Units in Package 3 66 Package 3 Height 30,000 cm Package 3 Width 30,000 cm Package 3 Length 40,000 cm Package 3 Weight 15,338 kg properties
iC60N - miniature circuit breaker - 2P - 6A - B curve
A9F73206
Definition of pole:3P
Nominal current (Ir):6 A
slope code:B
Compliance with industrial insulation according to IEC/EN 60947-2 standardCombines short circuit and overload current protectionVisitrip system for rapid detection of faulty outputs for shorter repair timesVisiSafe system offering advanced security when it comes to circuit protectionOption to add auxiliary devices, remote monitoring and residual current device (Vigi)Environmental performance of the productMore information