A9F74240
A9F74240 - scheinder
iC60N - miniature circuit breaker - 2P - 40A - C curve
stock :231description
Rated short-circuit breaking capacity up to 20kA at 220VAC to 240VAC per Standard EN/IEC 60947-2 and up to 6000A at 400VAC per Standard EN/IEC 60898-1 for both industrial Standard EN/IEC 60898-1 and residential Complies with standard EN/IEC 60947-2 This miniature circuit breaker protects circuits against short circuit and overload current Unique Visitrip indicator reduces response time by indicating faulty circuit Visisafe green stripe,guarantees the physical opening of the contacts to allow for downstream maintenance Quick closing mechanism independent of manual operation prolongs the service life Electrical withstand up to 10000 cycles and mechanical strength up to 20000 cycles Ui rated insulation voltage is 500VAC Limitation class 3 (EN/IEC60898-1' e) increases the cost of downstream circuit protection The product can be clipped to the DIN rail Width at 9mm level 4 Overvoltage category IV Product color is white (RAL9003) Dimensions (W) 36mm x (H) 85mm x (D) 78.5mm Weight 0.25kg According to IEC 60529 Standard , degree of protection in the box IP20 and IP40 Operating temperature -35°C to 70°C Storage temperature -40°C to 85°C.25kg According to IEC 60529 Standard, degree of protection in the box IP20 and IP40 Operating temperature -35°C to 70°C Storage temperature -40°C to 85°C.25kg According to IEC 60529 Standard, degree of protection in the box IP20 and IP40 Operating temperature -35°C to 70°C Storage temperature -40°C to 85°C.
Specifications Main
Main
device application Distribution sherry Act 9 product name Acti9 iC60 Product or component type Miniature circuit breaker Product group IC60N Definition of pole 2P number of protected poles 2 [In] nominal current 40 A Network type DC
ACopening unit technology Thermal Magnetic slope code C cutting capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at < = 125 V DC conforming to EN/IEC 60947-2
10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220...240 V AC 50/ 60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2Usage category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for insulation Yes conforming to TR 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2Standards TR 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complement
Network frequency 50/60Hz magnetic opening limit 8 x In +/- 20% [Ics] nominal service interrupting capacity 15 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 - 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz
27 kA 75 % conforming
to IEC 60947-2 - 12...133 V AC 50/60 Hz 27 kA 75 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
6000 A 100 % conforming to TR 60898-1 - 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 - 72...125 V DC
10 kA 100 % conforming to EN 60947-2 - 72...125 V DCrestriction class 3 conforming to TR 60898-1
3 conforming to IEC 60898-1[Ui] nominal insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage Conforming to 6 kV EN 60947-2
Conforming to 6 kV IEC 60947-2ignition position indicator Yes Control type Transition On-device signaling Open indicator Mounting Type Still mounting support DIN rail comb busbar distribution block compatibility Top or bottom: YES 9mm screw pitch 4 Height 85mm Width 36mm Depth 78.5mm Product weight 0.25kg colour White Mechanical durability 20000 cycles electrical resistance 10000 cycles connections - terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connection tightening torque 3.5 Nm top or bottom earth leakage protection Separate block Environment and Packing Units
Environment
IP protection degree
IP20 conforming to IEC 60529degree of contamination 3 conforming to EN 60947-2
3 conforming to IEC 60947-2overvoltage category IV tropical climate 2 conforming to IEC 60068-1 relative humidity 95% at 55 °C working height 0...2000m Nominal operating ambient temperature -35…70 °C Storage environmental conditions -40…85 °C Packaging units
Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 7,500 cm Package 1 Width 3,500 cm Package 1 Length 9,500 cm Package 1 Weight 239,000g Unit Type of Package 2 BB1 Number of Units in Package 2 6 Package 2 Height 8,000 cm Package 2 Width 9,600 cm Package 2 Length 22,500 cm Package 2 Weight 1,493 kg Unit Type of Package 3 S03 Number of Units in Package 3 66 Package 3 Height 30,000 cm Package 3 Width 30,000 cm Package 3 Length 40,000 cm Package 3 Weight 17,009 kg properties
iC60N - miniature circuit breaker - 2P - 40A - C curveA9F74240
Definition of pole:2P
Nominal current (Ir):40 A
slope code:C
- Compliance with industrial insulation according to IEC/EN 60947-2 standard
- Combines short circuit and overload current protection
- Visitrip system for rapid detection of faulty outputs for shorter repair times
- VisiSafe system offering advanced security when it comes to circuit protection
- Option to add auxiliary devices, remote monitoring and residual current device (Vigi)