A9F84310
A9F84310 - schneider
iC60H - miniature circuit breaker - 3P - 10A - C curve
stock: 30description
Rated short-circuit breaking capacity up to 30kA at 220VAC to 240VAC according to Standard EN/IEC 60947-2 and up to 10000A at 400VAC according to Standard EN/IEC 60898-1 Both industrial Standard EN/IEC 60898-1 Complies with residential Standard EN/IEC 60947-2 This miniature circuit breaker protects the circuit against short circuit and overload current Unique Visitrip indicator shows faulty circuit reducing response time Visisafe green stripe,guarantees physical opening of the contacts to allow for downstream maintenance Quick closing mechanism independent of manual operation prolongs service life Electrical withstand up to 10000 cycles and mechanical strength up to 20000 cycles Ui rated insulation voltage is 500VAC Limitation class 3 (EN/IEC60898-1' e) increases the cost of downstream circuit protection The product can be clipped to the DIN rail Width at 9mm level 6 Overvoltage category IV Product color is white (RAL9003) Dimensions (W) 54mm x (H) 85mm x (D) 78.5mm Weight 0.375kg IP20 degree of protection at terminals (according to IEC/EN 60529) Operating temperature -35°C to 70°C Storage temperature -40°C to 85°C.375kg Terminals have IP20 degree of protection (according to IEC/EN 60529) Operating temperature -35°C to 70°C Storage temperature -40°C to 85°C.375kg Terminals have IP20 degree of protection (according to IEC/EN 60529) Operating temperature -35°C to 70°C Storage temperature -40°C to 85°C.
Specifications Main
Main
device application Distribution sherry Act 9 product name Acti9 iC60 Product or component type Miniature circuit breaker Product group IC60H Definition of pole 3P number of protected poles 3 [In] nominal current 10 A Network type AC
DCopening unit technology Thermal Magnetic slope code C cutting capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2Usage category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for insulation Yes conforming to TR 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2Standards EN 60947-2
IEC 60898-1
IEC 60947-2
TR 60898-1Complement
Network frequency 50/60Hz magnetic opening limit 8 x In +/- 20% [Ics] nominal service interrupting capacity 15 kA 50 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 - 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 - 380 ...415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz
7500 A 75 % conforming to TR 60898-1 - 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 - 125...180 V DC
15 kA 100 % conforming to EN 60947-2 - 125...180 V DCrestriction class 3 conforming to TR 60898-1
3 conforming to IEC 60898-1[Ui] nominal insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage Conforming to 6 kV EN 60947-2
Conforming to 6 kV IEC 60947-2ignition position indicator Yes Control type Transition On-device signaling Open indicator Mounting Type Still mounting support DIN rail comb busbar distribution block compatibility Top or bottom: YES 9mm screw pitch 6 Height 85mm Width 54mm Depth 78.5mm Product weight 0.375 kg colour White Mechanical durability 20000 cycles electrical resistance 10000 cycles connections - terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connection tightening torque 2 Nm above or below earth leakage protection Separate block Environment and Packing Units
Environment
IP protection degree
IP20 conforming to IEC 60529degree of contamination 3 conforming to EN 60947-2
3 conforming to IEC 60947-2overvoltage category IV tropical climate 2 conforming to IEC 60068-1 relative humidity 95% at 55 °C working height 0...2000m Nominal operating ambient temperature -35…70 °C Storage environmental conditions -40…85 °C Packaging units
Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 7.5 cm Package 1 Width 5.5 cm Package 1 Length 9.5 cm Package 1 Weight 328.0g Unit Type of Package 2 BB1 Number of Units in Package 2 4 Package 2 Height 8.0 cm Package 2 Width 9.6 cm Package 2 Length 22.5 cm Package 2 Weight 1,367 kg Unit Type of Package 3 S03 Number of Units in Package 3 44 Package 3 Height 30.0 cm Package 3 Width 30.0 cm Package 3 Length 40.0 cm Package 3 Weight 15,524 kg properties
iC60H - miniature circuit breaker - 3P - 10A - C curveA9F84310
Definition of pole:3P
Nominal current (Ir):10 A
slope code:C
Compliance with industrial insulation according to IEC/EN 60947-2 standardCombines short circuit and overload current protectionVisitrip system for rapid detection of faulty outputs for shorter repair timesVisiSafe system offering advanced security when it comes to circuit protectionOption to add auxiliary devices, remote monitoring and residual current device (Vigi)Environmental performance of the productMore informationSustainable by Design