A9L65601
A9L65601 - schneider
iPRD65r modular surge arrester - 3P + N - 350V - with remote transfert
stock: 38
Description
This Acti9 iPRD65r surge arrester protects 3P+N installations. It allows quick replacement of damaged cartridges. This Type 2 device is recommended for very high risk level and incoming panel board. It offers remote reporting of the "cartridge must be changed" message. It can be turned over to allow the phase/neutral/earth cables to enter through either the top or the bottom. The associated circuit breaker Isc breaking capacity can go up to 50kA. It is compatible with TT and TN-S earthing system. The Imax rated discharge current is 65kA. The In nominal discharge current is 20kA. The Uc maximum continuous operating voltage in common mode is 260VAC between neutral and earth, and 350VAC between phase and earth. The Uc maximum continuous operating voltage in differential mode (between phase and neutral) is 350VAC. The Up Voltage protection level is 1.5kV in common mode (N/PE) and in differential mode (L/N). The Un rated service voltage is 230VAC or 400VAC. The operating frequency is 50Hz or 60Hz. The dimensions are (W) 72mm x (H) 85mm x (D) 69mm. The width in 9mm pitches is 8. The weight is 450g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C. This product complies with IEC 61643-11:2011 and EN61643-11:2012 standards.
Specifications Main
Main range of product Acti9 Product name Acti9 iPRD Product or component type Surge arrester with pluggable cartridge Device short name iPRD65r Device application Distribution Standards EN 61643-11:2012
IEC 61643-11:2011Product certifications CE Quality labels NF
KEMA-KEURPoles description 3P + N Remote signalling With Signal contacts composition 1 SD (1 C/O) Surge arrester type Electrical distribution network Earthing system TN-S
TTComplementary Surge arrester class type Type 2 Surge arrester technology MOV + GDT [Ue] rated operational voltage 230/400 V AC (+/- 10 %) at 50/60 Hz [In] nominal discharge current Common mode: 20 kA (L/PE)
Common mode: 20 kA (N/PE)
Differential mode: 20 kA (L/N)[Imax] maximum discharge current Common mode: 65 kA L/PE
Common mode: 65 kA N/PE
Differential mode: 65 kA L/N[Uc] maximum continuous operating voltage Common mode: 260 V N/PE
Common mode: 350 V L/PE
Differential mode: 350 V L/NMaximum [Up] voltage protection level Common mode <1.5 kV type 2 N/PE
Differential mode <1.5 kV type 2 L/N[Ut] temporary overvoltage 337 V L/N 5 s withstand
1200 V N/PE 200 ms safe failure mode
442 V L/PE 5 s withstand
1453 V L/PE 200 ms safe failure modeDisconnector device type Associated circuit breaker IC60N 50 A curve C - Icu 10 kA
Associated circuit breaker iC60H 50 A curve C - Icu 15 kA
Associated circuit breaker NG125N 50 A curve C - Icu 25 kA
Associated circuit breaker NG125H 50 A curve C - Icu 36 kA
Associated circuit breaker NG125L 50 A curve C - Icu 50 kA
Associated fuse gG 80 A - Icu 50 kASignalling circuit voltage 0.25 A/250 V AC 50/60 Hz Mounting mode Clip-on (DIN rail) 9 mm pitches 8 Height 85 mm Width 72 mm Depth 69 mm Product weight 0.492 kg Colour White (RAL 9003) [Ipe] Ground residual current 0.003 mA
0.6 mAConnections - terminals Tunnel type terminal (downside) 2.5…35 mm²
Tunnel type terminal (upside) 2.5…35 mm²Tightening torque 2.5 N.m Environment and Packing Units
Environment IK degree of protection IK03 conforming to IEC 62262 Relative humidity 5…95 % Operating altitude 2000 m Ambient air temperature for operation -25…60 °C Ambient air temperature for storage -40…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 8.0 cm Package 1 Width 8.0 cm Package 1 Length 9.0 cm Package 1 Weight 519.0 g Unit Type of Package 2 BB1 Number of Units in Package 2 3 Package 2 Height 9 cm Package 2 Width 10 cm Package 2 Length 27 cm Package 2 Weight 1.623 kg Unit Type of Package 3 S03 Number of Units in Package 3 27 Package 3 Height 30 cm Package 3 Width 30 cm Package 3 Length 40 cm Package 3 Weight 15.123 kg properties
iPRD65r modular surge arrester - 3P + N - 350V - with remote transfert
A9L65601
Poles description: 3P + N
Earthing system: TN-CTN-STT
Recommended for a very high risk level (strongly exposed site) in incoming panel board
Type 2 65kA surge arrester according to IEC 61643-11:2011 and EN 61643-11:2012 standards
Suitable for TT and TN-S networks with high prospective short-circuit fault currents
Fitted with a remote transfer contact to send cartridge must be replaced indication information
Easy to replace withdrawable cartridges, and pluggable with anti-vibration lock