Vigi C120 - earth leakage add-on block - 2P - 30 mA - class A
stock:9
description
Earth leakage The protection class is AC type with 30mA sensitivity and voltage independent technology This product provides protection against short circuit, cable overload, electric shock due to indirect contact and fire hazards This product complies with EN 61009 Standard Electrical durability is up to 20000 cycles Ue rated operating voltage is 230VAC to 240VAC Ui rated insulation voltage is 500VAC Uimp rated impulse withstand voltage is 6kV Pollution degree 3 Can be mounted on 35mm symmetrical DIN rail Width at 9mm levels is 7 Product colour is white (RAL9003) Weight 0.325kg Degree of protection IP20 and IP40 in a box Operating temperature -5°C to 60°C Storage temperature -40°C to 60°C.