top of page
A9R41240

A9R41240

SKU: TR
$26.94Price

A9R41240  - schneider

Acti9 iID Residual Current Relay - 2 Pole 40A 30mA AC Type

stock: 42

description

This product protects against electric shock and fire hazards through direct or indirect contact. It performs the function of disconnecting electrical circuits in case of earth fault. The unique Visitrip indicator shows the faulty device with a mechanical indicator on the front, thus reducing response time.The cable end has a VisiSafe window with a green stripe indicating full polarity and allows for downstream maintenance This product complies with Standard EN/IEC 61008-1 (Im/IΔm) rated breaking and short-circuit capacity 1500A (Inc/ IΔc) conditional rated short-circuit current is 10kA Electrical endurance is up to 15000 cycles Mechanical endurance is up to 20000 cycles Ue operating voltage is 220VAC to 240VAC Ui rated insulation voltage is 500VAC Uimp rated impulse withstand voltage is 6kV DIN rail mountable width 4 at 9mm level Product color is white (RAL9003) Dimensions (W) 36mm x (H) 91mm x (D) 73.5mm Weight 0.21kg Has IP20 degree of protection Once in a modular box IP40 according to IEC/EN 60529 Standard Operating temperature -5°C to 60° C. Storage temperature -40°C to 85°C.

  • Specifications Main

    Main

    Sherry Act 9
    Product Name Acti9 iID
    Product or Component Type Residual current circuit breaker (RCCB)
    Product Group IID
    Definition of Pole 2P
    neutral position Left
    [In] nominal current 40 A
    Network Type HUNGRY
    earth leakage sensitivity 30mA
    earth leakage protection time delay Momentary
    earth leakage protection class AC type

    Complement

    location of the device in the system Exit
    Network Frequency 50/60Hz
    [Ue] nominal operating voltage 220...240V AC 50/60Hz
    residual current tripping technology Voltage independent
    hominal cutting and closing capacity Idm 1500 A
    Idm 1500 A
    rated conditional short-circuit current 10 kA
    [Ui] nominal insulation voltage 500V AC 50/60Hz
    [Uimp] rated impulse withstand voltage 6 kV
    interruption current 250 A
    ignition position indicator Yes
    Control type Transition
    Mounting Type Pluggable
    Mounting Support DIN rail
    9mm screw pitch 4
    Height 91mm
    Width 36mm
    Depth 73.5mm
    Product Weight 0.21 kg
    colour White
    Mechanical durability 20000 cycles
    electrical resistance AC-1: 15000 cycles
    Locking options definition Locking device
    connections - terminals Single terminal top or bottom1…35 mm² rigid
    Single terminal top or bottom1…25 mm² flexible
    Single terminal top or bottom1…25 mm² ferrule and flexible
    wire stripping length 14 mm for top or bottom connection
    tightening torque 3.5 Nm top or bottom
  • Environment and Packing Units

    Environment

    Standards EN/IEC 61008-1
    EN/IEC 61008-2-1
    IP protection degree IP20 conforming to IEC 60529
    IP40 (modular enclosure) conforming to IEC 60529
    degree of contamination 3
    electromagnetic compatibility 8/20 µs impulse resistance, 250 A conforming to EN/IEC 61008-1
    ambient air temperature for operation -5…60 °C
    Storage Environmental Conditions -40…85 °C

    Packaging units

    Unit Type of Package 1 PCE
    Number of Units in Package 1 1
    Package 1 Height 4,000 cm
    Package 1 Width 8,500 cm
    Package 1 Length 10,000 cm
    Package 1 Weight 210,700g
    Unit Type of Package 2 S03
    Number of Units in Package 2 54
    Package 2 Height 30,000 cm
    Package 2 Width 30,000 cm
    Package 2 Length 40,000 cm
    Package 2 Weight 11,773 kg
    Unit Type of Package 3 P12
    Number of Units in Package 3 432
    Package 3 Height 45,000 cm
    Package 3 Width 80,000 cm
    Package 3 Length 120,000 cm
    Package 3 Weight 106,198 kg
  • properties

    Acti9 iID Residual Current Relay - 2 Pole 40A 30mA AC Type

    A9R41240

    Pole Definition:2P

    Nominal current (Ir):40 A

    earth leakage protection class:AC type

    Earth leakage sensitivity:30mA

    Protection of persons against electric shock by direct contact
    Residential insulation in accordance with IEC 61008-1 and IEC 61008-2-1 standards
    Easy installation with unified terminal design and wiring indicator
    Ground fault indication with red mechanical indicator on the front face
    Compatible with Acti9 captive lock accessory
No Reviews YetShare your thoughts. Be the first to leave a review.