Vigi iC60 - earth leakage add-on block - 2P - 40A - 300mA - AC type
stock: 77
Description
This Acti9 Vigi iC60 is a modular add-on residual current devices. It is a 2P, rated current is 40A, operating voltage is 230VAC to 415VAC according to IEC 61009-1. The earth leakage protection class is AC type with a sensitivity of 300mA and a voltage independent technology. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. A VisiTrip window is here to indicate a fault tripping by a red mechanical indicator on the front face. It can be combined with iC60 or Acti9 Reflex iC60, to provide protection of persons and protection of installations. This product is compliant with IEC 61009-1 and EN 61009-1 standard. The Ue rated operational voltage is 230VAC or 400VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 6kV. The pollution degree is 3. It can be mounted on DIN rail. The width in 9mm pitches is 4. The dimensions are (W) 72mm x (H) 91mm x (D) 73.5mm. The weight is 0.165kg. The degree of protection is IP20 and IP40 in an enclosure. The operating temperature -5°C to +60°C. The storage temperature is -40°C to +85°C.
Specifications Main
Main Range Acti9 product or component type Add-on residual current devices Device short name Vigi iC60 Poles description 2P [In] rated current 40 A Earth-leakage sensitivity 300 mA Earth-leakage protection time delay Instantaneous Earth leakage protection type Type AC Network type AC Network frequency 50/60 Hz [Ue] rated operational voltage 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1
230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1Standards EN/IEC 61009-1
EN/IEC 61009-2-19 mm pitches 4 Complementary Device location in system Outgoer Residual current tripping technology Voltage independent [Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2 Range compatibility Acti 9 Acti9 iC60
Acti 9 Acti9 Reflex iC60Product compatibility Single terminal Local signalling Trip indicator Mounting mode Clip-on Mounting support DIN rail Electrical connection to mcb By screws Comb busbar and distribution block compatibility Bottom: YES Height 91 mm Width 72 mm Depth 73.5 mm Net weight 0.165 kg Connections - terminals Tunnel type terminal downside for 1 cable(s) 1…35 mm² rigid without cable end
Tunnel type terminal downside for 1 cable(s) 1…25 mm² flexible without cable end
Tunnel type terminal downside for 1 cable(s) 1…25 mm² flexible with cable endWire stripping length 14 mm for bottom connection Tightening torque 3.5 N.m bottom Environment and Packing Units
Environment IP degree of protection IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529Pollution degree 3 conforming to IEC 60947-2 Electromagnetic compatibility 8/20 µs impulse withstand, 250 A conforming to IEC 61009-1 Ambient air temperature for operation -5…60 °C Ambient air temperature for storage -40…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 8.7 cm Package 1 Width 8.7 cm Package 1 Length 12.0 cm Package 1 Weight 161.0 g Unit Type of Package 2 S03 Number of Units in Package 2 27 Package 2 Height 30.0 cm Package 2 Width 30.0 cm Package 2 Length 40.0 cm Package 2 Weight 4.807 kg