ATV320U07N4C
ATV320U07N4C - schneider
variable speed drive, ATV320, 0.75 kW, 380…500 V, 3 phases, compact
stock: 10
Description
This Altivar 320 variable speed drive can feed 3-phase synchronous and asynchronous motors. Its compact form factor allows vertical stacking of drives inside machine frames. It works at a rated power up to 0.75kW / 1hp and a rated voltage from 380V to 500V AC. Its robust design with IEC 60721-3-3 class 3C3 coated printed circuit boards allows to extend machine availability in harsh environmental conditions, for example at ambient temperatures of up to 60°C without the need of additional cooling. It incorporates functions suitable for the most common applications, including torque and speed accuracy at very low speed, high dynamic performance with flux vector control without sensor and extended frequency range for high-speed motors. It also incorporates parallel connection of motors and special drives using the voltage/frequency ratio and static speed accuracy and energy saving for open-loop synchronous motors. The drive software includes 5 safety functions that help machines meet safety requirements, whether or not they are used in conjunction with a Preventa safety module. These safety functions are configured using SoMove software. Altivar Machine ATV320 was designed for Original Equipment Manufacturers (OEMs) that meets simple and advanced application requirements covered for packaging, material handling, textile, material working, mechanical actuators and hoisting. It conforms to international standards IEC/EN 61800-5-1 and IEC/EN 61800-3 (immunity and conducted and radiated EMC emissions). It is also CE, UL, CSA, NOM, EAC and RCM certified. Mounting accessories and external options (braking resistors, line chokes, motor chokes, additional EMC filters) are available with Altivar Machine ATV320 drives. The type of external accessories and options depends on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a panel, thanks to 4 fixing holes. It is fully integrated inside Schneider Electric’s EcoStruxure Machine through DTM. It is possible to configure, control, and diagnose ATV320 drives directly in SoMachine and SoMove software by means of the same software brick (DTM). It is eco-friendly and complies with directives such as RoHS, WEEE, etc.relating to environmental protection.
Specifications Main
Main range of product Altivar Machine ATV320 product or component type Variable speed drive Product specific application Complex machines Variant Standard version Format of the drive Compact mounting mode Wall mount communication port protocol Modbus serial
CANopenOption card Communication module, CANopen
Communication module, EtherCAT
Communication module, Profibus DP V1
Communication module, PROFINET
Communication module, Ethernet Powerlink
Communication module, EtherNet/IP
Communication module, DeviceNet[Us] rated supply voltage 380...500 V - 15...10 % Nominal output current 2.3 A Motor power kW 0.75 kW for heavy duty EMC filter Class C2 EMC filter integrated IP degree of protection IP20 Complementary Discrete input number 7 Discrete input type STO safe torque off, 24 V DC, impedance: 1.5 kOhm
DI1...DI6 logic inputs, 24 V DC (30 V)
DI5 programmable as pulse input: 0…30 kHz, 24 V DC (30 V)Discrete input logic Positive logic (source)
Negative logic (sink)Discrete output number 3 Discrete output type Open collector DQ+ 0…1 kHz 30 V DC 100 mA
Open collector DQ- 0…1 kHz 30 V DC 100 mAAnalogue input number 3 Analogue input type AI1 voltage: 0...10 V DC, impedance: 30 kOhm, resolution 10 bits
AI2 bipolar differential voltage: +/- 10 V DC, impedance: 30 kOhm, resolution 10 bits
AI3 current: 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration), impedance: 250 Ohm, resolution 10 bitsAnalogue output number 1 Analogue output type Software-configurable current AQ1: 0...20 mA impedance 800 Ohm, resolution 10 bits
Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10 bitsRelay output type Configurable relay logic R1A 1 NO electrical durability 100000 cycles
Configurable relay logic R1B 1 NC electrical durability 100000 cycles
Configurable relay logic R1C
Configurable relay logic R2A 1 NO electrical durability 100000 cycles
Configurable relay logic R2CMaximum switching current Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 250 V AC
Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 30 V DCMinimum switching current Relay output R1A, R1B, R1C, R2A, R2C: 5 mA at 24 V DC Method of access Slave CANopen 4 quadrant operation possible True Asynchronous motor control profile Voltage/frequency ratio, 5 points
Flux vector control without sensor, standard
Voltage/frequency ratio - Energy Saving, quadratic U/f
Flux vector control without sensor - Energy Saving
Voltage/frequency ratio, 2 pointsSynchronous motor control profile Vector control without sensor Transient overtorque 170…200 % of nominal motor torque Maximum output frequency 0.599 kHz Acceleration and deceleration ramps Linear
U
S
CUS
Ramp switching
Acceleration/deceleration ramp adaptation
Acceleration/deceleration automatic stop with DC injectionMotor slip compensation Automatic whatever the load
Adjustable 0...300 %
Not available in voltage/frequency ratio (2 or 5 points)Switching frequency 2...16 kHz adjustable
4...16 kHz with derating factorNominal switching frequency 4 kHz Braking to standstill By DC injection Brake chopper integrated True Line current 3.6 A at 380 V (heavy duty)
2.8 A at 500 V (heavy duty)Maximum input current 3.6 A Maximum output voltage 500 V Apparent power 2.4 kVA at 500 V (heavy duty) Network frequency 50...60 Hz Relative symmetric network frequency tolerance 5 % Prospective line Isc 5 kA Base load current at high overload 7.1 A Power dissipation in W Fan: 32.0 W at 380 V, switching frequency 4 kHz With safety function Safely Limited Speed (SLS) True With safety function Safe brake management (SBC/SBT) False With safety function Safe Operating Stop (SOS) False With safety function Safe Position (SP) False With safety function Safe programmable logic False With safety function Safe Speed Monitor (SSM) False With safety function Safe Stop 1 (SS1) True With sft fct Safe Stop 2 (SS2) False With safety function Safe torque off (STO) True With safety function Safely Limited Position (SLP) False With safety function Safe Direction (SDI) False Protection type Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overheating protection: drive
Short-circuit between motor phases: drive
Thermal protection: driveWidth 105.0 mm Height 142.0 mm Depth 158.0 mm net weight 1.2 kg Environment and Packing Units
Environment Operating position Vertical +/- 10 degree Product certifications CE
ATEX
NOM
GOST
EAC
RCM
KCmarking CE
ATEX
UL
CSA
EAC
RCMStandards IEC 61800-5-1 Electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11Environmental class (during operation) Class 3C3 according to IEC 60721-3-3
Class 3S2 according to IEC 60721-3-3Maximum acceleration under shock impact (during operation) 150 m/s² at 11 ms Maximum acceleration under vibrational stress (during operation) 10 m/s² at 13...200 Hz Maximum deflection under vibratory load (during operation) 1.5 mm at 2...13 Hz Permitted relative humidity (during operation) Class 3K5 according to EN 60721-3 Volume of cooling air 18.0 m3/h Overvoltage category III Regulation loop Adjustable PID regulator Speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tn Pollution degree 2 Ambient air transport temperature -25…70 °C Ambient air temperature for operation -10…50 °C without derating
50…60 °C with derating factorAmbient air temperature for storage -25…70 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 18.000 cm Package 1 Width 18.500 cm Package 1 Length 18.500 cm Package 1 Weight 1.680 kg Unit Type of Package 2 S06 Number of Units in Package 2 30 Package 2 Height 75.000 cm Package 2 Width 60.000 cm Package 2 Length 80.000 cm Package 2 Weight 63.490 kg