top of page
C10F42D100

C10F42D100

SKU: TR
$578.00Price

C10F42D100 - scheinder

Circuit breaker ComPacT NSX100F, 36kA at 415VAC, MicroLogic 2.2 trip unit 100A, 4 poles 4d

stock : 16

Description

This ComPacT NSX100F is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic MicroLogic 2.2 trip unit, with 100A rating. MicroLogic 2.2 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection. This 4 poles version (140mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX100F is part of Schneider Electric EcoStruxure Power architecture.

  • Specifications Main

    Main

    Range ComPacT new generation
    Product name ComPacT NSX new generation
    Device short name NSX100F
    product or component type Circuit breaker
    Device application Distribution
    Poles description 4P
    Protected poles description 4D
    3D + N/2
    3D
    Neutral position Left
    [In] rated current 100 A at 40 °C
    [Ue] rated operational voltage 690 V AC 50/60 Hz
    Network type AC
    Network frequency 50/60 Hz
    Suitability for isolation Yes conforming to EN/IEC 60947-2
    Utilisation category Category A
    [Icu] rated ultimate short-circuit breaking capacity 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
    22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
    8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    Performance level F 36 kA 415 V AC
    Trip unit name MicroLogic 2.2
    Trip unit technology Electronic
    Trip unit protection functions LSoI
    Control type Toggle
    Circuit breaker mounting mode Fixed
  • Complementary

    [Ui] rated insulation voltage 800 V AC 50/60 Hz
    [Uimp] rated impulse withstand voltage 8 kV
    [Ics] rated service short-circuit breaking capacity 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
    11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
    4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    Mechanical durability 50000 cycles
    Electrical durability 50000 cycles at 440 V In/2
    30000 cycles at 440 V In
    20000 cycles at 690 V In/2
    10000 cycles at 690 V In
    Power dissipation per pole 4.7 W
    Mounting support Backplate
    Mounting position Horizontal and vertical
    Flat on the back
    Upside connection Front
    downside connection Front
    Connection pitch 35 mm
    Protection type L : for overload protection (long time)
    So : for short time short-circuit protection with fixed delay
    I : for instantaneous short-circuit protection
    Trip unit rating 100 A at 40 °C
    Long-time pick-up adjustment type Ir (thermal protection) Adjustable 9 settings
    [Ir] long-time protection pick-up adjustment range 40...100 A
    Long-time protection delay adjustment type tr Fixed
    [tr] long-time protection delay adjustment range 400 s at 1.5 x Ir
    16 s at 6 x Ir
    11 s at 7.2 x Ir
    Neutral protection settings 0.5 x Ir (3D + N/2)
    1 x Ir (4D)
    No protection (3D)
    thermal memory 20 minutes before and after tripping
    Short-time protection pick-up adjustment type Isd Adjustable 9 settings
    [Isd] Short-time protection pick-up adjustment range 1.5...10 x And
    Short-time protection delay adjustment type tsd Fixed
    Instantaneous protection pick-up adjustment type Ii Fixed
    [Ii] instantaneous protection pick-up adjustment range 1500 A
    earth-leakage protection Without
    Zone selective interlocking ZSI Without
    Number of slots for electrical auxiliaries 5 slot(s)