C10R3TM100
C10R3TM100 - SCHNEIDER
Circuit breaker, ComPacT NSX100R, 200kA/415VAC, 3 poles, TMD trip unit 100A
In Stock
Description
Breaking capacity (Icu) 200kA rms / 415VAC 50/60Hz and 45kA rms / 690VAC 50/60Hz Operating voltage 690VAC 50/60Hz This product includes a 100A rated thermal-magnetic trip unit (TMD) TMD trip unit, an adjustable thermal overload This 3-pole version (105 mm x 161 mm x 86 mm) comes with a variety of optional functions and accessories Complies with international standards (IEC 60947), CCC, EAC and marine specifications ComPacT NSX100R Schneider Electric EcoStruxure It is part of the Power architecture.
Specifications
Range ComPacT new generation Product name ComPacT NSX new generation Device short name NSX100R product or component type Circuit breaker Device application Distribution Poles description 3P Protected poles description 3D [In] rated current 100 A at 40 °C [Ue] rated operational voltage 690 V AC 50/60 Hz Network type AC Network frequency 50/60 Hz Suitability for isolation Yes conforming to EN/IEC 60947-2 Utilisation category Category A [Icu] rated ultimate short-circuit breaking capacity 200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2Performance level R 200 kA 415 V AC Trip unit name TM-D Trip unit technology Thermal-magnetic Trip unit protection functions LI Control type Toggle Circuit breaker mounting mode Fixed Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 8 kV [Ics] rated service short-circuit breaking capacity 200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2Mechanical durability 20000 cycles Electrical durability 20000 cycles at 440 V In/2
10000 cycles at 440 V In
10000 cycles at 690 V In/2
5000 cycles at 690 V InPower dissipation per pole 8.8 W Mounting support Backplate Mounting position Horizontal and vertical
Flat on the backUpside connection Front downside connection Front Connection pitch 35 mm Protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)Trip unit rating 100 A at 40 °C Long-time pick-up adjustment type Ir (thermal protection) Adjustable [Ir] long-time protection pick-up adjustment range 0.7...1 x In Long-time protection delay adjustment type tr Fixed [tr] long-time protection delay adjustment range 120…400 s at 1.5 x In
15 s at 6 x IrInstantaneous protection pick-up adjustment type Ii Fixed [Ii] instantaneous protection pick-up adjustment range 800 A earth-leakage protection Without Number of slots for electrical auxiliaries 5 slot(s) Width (W) 105 mm Height (H) 161 mm Depth (D) 86 mm net weight 2.05 kg Environmental
Standards EN/IEC 60947 Product certifications Marine
EAC
CCCOvervoltage category Class II Electrical shock protection class Class II Pollution degree 3 conforming to IEC 60664-1 IP degree of protection IP40 conforming to IEC 60529 IK degree of protection IK07 conforming to IEC 62262 Ambient air temperature for operation -25…70 °C ambient air temperature for storage -50…85 °C Relative humidity 0…95 % Operating altitude 0...2000 m without derating
2000 m...5000 m with derating