C40N4
C40N4 - schneider
circuit breaker basic frame, ComPacT NSX400N, 50 kA at 415 VAC 50/60 Hz, 400 A, without trip unit, 4 poles
stock: 50
Description
This is a 4 poles basic frame for ComPacT NSX400N. ComPacT NSX is designed to optimize space and breaking capacity for all standard and specific applications. This basic frame comes without trip unit, and is compatible with any type of trip unit which has to be ordered separately The breaking capacity Icu is 50kA at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz (limited to 440VAC 50/60Hz if there is an earth-leakage protection). It can be equipped with a variety of optional functions and accessories. The dimensions are 185mm x 255mm x 110mm. It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX400N is part of Schneider Electric EcoStruxure Power architecture.
Specifications Main
Main Range ComPacT new generation Product name ComPacT NSX new generation Device short name NSX400N Product or component type Basic frame Device application Distribution Poles description 4P Neutral position Left [In] rated current 400 A at 40 °C [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 Network type AC Network frequency 50/60 Hz Suitability for isolation Yes conforming to EN/IEC 60947-2 Utilisation category Category A [Icu] rated ultimate short-circuit breaking capacity 85 kA at 240 V AC 50/60 Hz conforming to UL 508
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 480 V AC 50/60 Hz conforming to UL 508
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 600 V AC 50/60 Hz conforming to UL 508
42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2Performance level N 50 kA 415 V AC Control type Toggle Mounting mode Fixed Complementary [Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2 [Ics] rated service short-circuit breaking capacity 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2Mechanical durability 15000 cycles conforming to IEC 60947-2 Electrical durability 12000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
3000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
6000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2Mounting support Backplate Upside connection Front Downside connection Front Connection pitch 45 mm Protection type Without protection Width (W) 185 mm Height (H) 255 mm Depth (D) 110 mm Environment and Packing Units
Environment Standards EN/IEC 60947-2
UL 60947-4-1Pollution degree 3 conforming to IEC 60664-1 IP degree of protection IP40 conforming to IEC 60529 IK degree of protection IK07 conforming to IEC 62262 Ambient air temperature for operation -25…70 °C Ambient air temperature for storage -50…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 15.000 cm Package 1 Width 20.000 cm Package 1 Length 29.000 cm Package 1 Weight 5.818 kg Unit Type of Package 2 P12 Number of Units in Package 2 28 Package 2 Height 44.000 cm Package 2 Width 80.000 cm Package 2 Length 120.000 cm Package 2 Weight 176.000 kg properties
circuit breaker basic frame, ComPacT NSX400N, 50 kA at 415 VAC 50/60 Hz, 400 A, without trip unit, 4 poles
C40N4
Poles description: 4P
Breaking capacity: 50 kA
EAN Code: 3606482003163
Schneider Electric green signature style for the entire ComPacT range
Estimated 40% reduction of wiring time for panel builders"
Experience easier installation thanks to a new ergonomic front-plate design"
notification_ok
"Gain the confidence that all auxiliaries are on the right spot, and check that you have the right coil rating"
notification_ok
"Ergonomic new toggle for easier breaker manual operation"
Read less
Environmental Data
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
360
BVB
information_stroke
Accepted
China Green Designed Product
information_stroke
Yes
Use Better
Packaging made with recycled cardboard
information_stroke :Yes
Use Again
Take-back
information_stroke: No