CA2KN31M7 - SCHNEIDER

TeSys K control relay - 3 NO + 1 NC - <= 690 V - 220...230 V AC coil

In Stock

Description

 

Provides high reliability and durability for high operating speeds up to 180 rpm and ambient temperature -25/+50°C Compact (45 mm width) for mounting on a 35 mm DIN rail or fixing with screws Multi standard certified (IEC, UL, CSA) , CCC, EAC), is a Green Premium product (RoHS/REACh).

 

sherryTeSys
Name of the productTeSys CAK
Product or component typeControl relay
Product groupCA2K
contactor applicationControl circuit
usage categoryAC-15
DC-13
pole contact regulation3 NC + 1 NC
[Ue] nominal operating voltage<= 690 V <= 400 Hz
control circuit typeAC at 50/60 Hz
control circuit voltage220...230 V AC 50/60 Hz
  • Specifications

    sherry TeSys
    Name of the product TeSys CAK
    Product or component type Control relay
    Product group CA2K
    contactor application Control circuit
    usage category AC-15
    DC-13
    pole contact regulation 3 NC + 1 NC
    [Ue] nominal operating voltage <= 690 V <= 400 Hz
    control circuit type AC at 50/60 Hz
    control circuit voltage 220...230 V AC 50/60 Hz
  • Environmental

    standards EN/IEC 60947-4-1
    GB/T 14048.4
    UL 60947-4-1
    CSA C22.2 No 60947-4-1
    JIS C8201-4-1
    Product certifications CB Scheme
    CCC
    UL
    CSA
    EAC
    CE
    UKCA
    IP protection degree IP2X
    preventive maintenance TC conforming to IEC 60068
    ambient air temperature for operation -25…50 °C
    Storage environmental conditions -50…80 °C
    working height Without 2000m
    flame delayer Conforming to V1UL 94
    Conforming to Requirement 2NF F 16-101
    Conforming to Requirement 2NF F 16-102
    mechanical durability Vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Shocks contactor open: 11 to 10 ms Gn conforming to IEC 60068-2-27
    Shocks contactor closed: 11 ms for 15 Gn conforming to IEC 60068-2-27

    Packaging units

  • Complementary

    [Ith] classic open air thermal current 10 A (at 50 °C)
    Irms nominal closing capacity 110 A conforming to IEC 60947
    relevant insurance value 10 A gG conforming to IEC 60947
    10 A gG conforming to VDE 0660
    [Ui] nominal insulation voltage Conforming to 690 V Conforming to IEC 60947
    750 V Conforming to VDE 0110 group C
    Conforming to 690 V BS 5424
    Conforming to 600 V CSA C22.2 No 14
    mounting support Plate
    Rail
    connections - terminals Screw clamp terminals 1 cable(s) 1.5…4 mm²solid
    Screw clamp terminals 2 cable(s) 1.5…4 mm²solid
    Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible
    Screw clamp terminals 2 cable(s) ) 0.75…4 mm²flexible without cable end
    Screw clamp terminals 1 cable(s) 0.34…1.5 mm²flexible with
    screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible without cable end
    tightening torque 1.3 Nm - on screw clamp terminals - flat with screwdriver Ø 6 mm
    1.3 Nm - on screw clamp terminals - Philips No 2 with screwdriver 6 mm
    1.3 Nm - on screw clamp terminals - posidriv No 2 with screwdriver
    control circuit voltage limits Drop: 0.2...0.75 Uc (at <50 °C)
    Operating: 0.8...1.15 Uc (at <50 °C)
    operation time 10...20 ms coil de-energization and NC opening
    10...20 ms coil energization and NC closing
    15...25 ms coil de-energization and NC closing
    5...15 ms coil energization and NC opening
    Mechanical durability 10 Mcycles
    Maximum operating speed 10000 cyc/h
    immunity to microfractures 2ms
    Starting power in VA 30 VA (at 20 °C)
    Holding power consumption in VA 4.5 VA (at 20 °C)
    heat dissipation 1.3W