CAE22B5
SKU: TR
$9.00Price
CAE22B5 - SCHNEIDER
Easy TeSys control relay - 2 NO + 2 NC <= 690 V - 24 VAC
In Stock
Description
EasyPact TVS control relay for utilization categories AC-15/AC-14 up to 10A/690V. It provides 4 instantaneous contacts (2NO+2NC), a 24V 50Hz AC coil, connections by screw clamp terminals. For demanding applications with standard operating rates until 3 cycles/second, it procures standard reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach).
Specifications
Range Easy TeSys Range of product Easy TeSys Control Relay product or component type Control relay Device short name CAE contactor application Control circuit Colour Grey (RAL 7011) Complementary
Main Range Easy TeSys Range of product Easy TeSys Control Relay product or component type Control relay Device short name CAE contactor application Control circuit Colour Grey (RAL 7011) Complementary Utilisation category AC-15
AC-14Pole contact composition 2 NO + 2 NC [Ue] rated operational voltage <= 690 V AC Control circuit type AC at 50 Hz [Uc] control circuit voltage 24 V AC 50 Hz [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947 [Ith] conventional free air thermal current 10 A (at 40 °C) Irms rated making capacity 140 A at 690 V AC conforming to IEC 60947-5-1 [Icw] rated short-time withstand current 120 A - 500 ms
140 A - 100 msAssociated fuse rating 10 A gG at 690 V conforming to IEC 60947-5-1 [Ui] rated insulation voltage 690 V conforming to IEC 60947-5-1 Mounting support Rail
PlateConnections - terminals Screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end
Screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end
Screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
Screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end
Screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable endRecommended tightening torque 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit voltage limits Operational: 0.85...1.1 Uc at 50 Hz
Drop-out: 0.3...0.6 UcOperating time 4...19 ms coil energisation and NC opening
12...22 ms coil energisation and NO closing
4...12 ms coil de-energisation and NC opening
6...17 ms coil de-energisation and NO closingMechanical durability 10 Mcycles Maximum operating rate 180 cyc/mn Inrush power in VA 70 VA 50 Hz (at 20 °C) Hold-in power consumption in VA 8 VA 50 Hz (at 20 °C) Minimum switching voltage 17 V Minimum switching current 5 mA Non-overlap time 1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contactInsulation resistance > 10 MOhm Mechanical robustness Shocks control relay open: 7 Gn for 11 ms
Shocks control relay closed: 10 Gn for 11 ms
Vibrations control relay open: 1.5 Gn, 5...300 Hz
Vibrations control relay closed: 3 Gn, 5...300 HzHeight 74 mm Width 45 mm Depth 80 mm net weight 0.28 kg Environmental
Standards IEC 60947-5-1 Product certifications GOST IP degree of protection IP2X conforming to IEC 60529 Protective treatment TH conforming to IEC 60068 Ambient air temperature for operation -20…70 °C ambient air temperature for storage -60…80 °C Operating altitude 3000 m without derating