CAE22B5 - SCHNEIDER

Easy TeSys control relay - 2 NO + 2 NC <= 690 V - 24 VAC

In Stock

Description

EasyPact TVS control relay for utilization categories AC-15/AC-14 up to 10A/690V. It provides 4 instantaneous contacts (2NO+2NC), a 24V 50Hz AC coil, connections by screw clamp terminals. For demanding applications with standard operating rates until 3 cycles/second, it procures standard reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach).

  • Specifications

    Range Easy TeSys
    Range of product Easy TeSys Control Relay
    product or component type Control relay
    Device short name CAE
    contactor application Control circuit
    Colour Grey (RAL 7011)
  • Complementary

    Main
    Range Easy TeSys
    Range of product Easy TeSys Control Relay
    product or component type Control relay
    Device short name CAE
    contactor application Control circuit
    Colour Grey (RAL 7011)
    Complementary
    Utilisation category AC-15
    AC-14
    Pole contact composition 2 NO + 2 NC
    [Ue] rated operational voltage <= 690 V AC
    Control circuit type AC at 50 Hz
    [Uc] control circuit voltage 24 V AC 50 Hz
    [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
    [Ith] conventional free air thermal current 10 A (at 40 °C)
    Irms rated making capacity 140 A at 690 V AC conforming to IEC 60947-5-1
    [Icw] rated short-time withstand current 120 A - 500 ms
    140 A - 100 ms
    Associated fuse rating 10 A gG at 690 V conforming to IEC 60947-5-1
    [Ui] rated insulation voltage 690 V conforming to IEC 60947-5-1
    Mounting support Rail
    Plate
    Connections - terminals Screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end
    Screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end
    Screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
    Screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
    Screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end
    Screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end
    Recommended tightening torque 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
    Control circuit voltage limits Operational: 0.85...1.1 Uc at 50 Hz
    Drop-out: 0.3...0.6 Uc
    Operating time 4...19 ms coil energisation and NC opening
    12...22 ms coil energisation and NO closing
    4...12 ms coil de-energisation and NC opening
    6...17 ms coil de-energisation and NO closing
    Mechanical durability 10 Mcycles
    Maximum operating rate 180 cyc/mn
    Inrush power in VA 70 VA 50 Hz (at 20 °C)
    Hold-in power consumption in VA 8 VA 50 Hz (at 20 °C)
    Minimum switching voltage 17 V
    Minimum switching current 5 mA
    Non-overlap time 1.5 ms on energisation between NC and NO contact
    1.5 ms on de-energisation between NC and NO contact
    Insulation resistance > 10 MOhm
    Mechanical robustness Shocks control relay open: 7 Gn for 11 ms
    Shocks control relay closed: 10 Gn for 11 ms
    Vibrations control relay open: 1.5 Gn, 5...300 Hz
    Vibrations control relay closed: 3 Gn, 5...300 Hz
    Height 74 mm
    Width 45 mm
    Depth 80 mm
    net weight 0.28 kg
  • Environmental

    Standards IEC 60947-5-1
    Product certifications GOST
    IP degree of protection IP2X conforming to IEC 60529
    Protective treatment TH conforming to IEC 60068
    Ambient air temperature for operation -20…70 °C
    ambient air temperature for storage -60…80 °C
    Operating altitude 3000 m without derating