EZC100H3030
EZC100H3030 - scheinder
circuit breaker Easypact EZC100H - TMD - 30 A - 3 poles 3d
stock : 74
Description
EasyPact EZC100H is a 3-pole fixed circuit breaker designed for protection of low voltage electrical installations Used for standard applications in industries and buildings and offers good performance against competitive price Breaking capacity (Icu) is 30kA rms at 415VAC 50/60Hz Operating voltage 550VAC 50 /60Hz or 250VDC Thermal-magnetic trip unit rated 30A Trip unit provides constant overload and instantaneous protections This 3-pole version (75mm x 130mm x 60mm) comes with various optional functions and accessories Easypact EZC100H complies with international standards (IEC 60947, UL 508) and maritime certifications
Specifications Main
Main Range of product EasyPact Product or component type Circuit breaker Device short name Easypact EZC100H Circuit breaker name Easypact EZC100H Device application Distribution poles description 3P Protected poles description 3t Network type AC
DCNetwork frequency 50/60 Hz [In] rated current 30 A at 40 °C [Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2 [Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2Breaking capacity code H Breaking capacity 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2
10 kA Icu at 250 V DC 2P conforming to IEC 60947-2
10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 15 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 125 V DC conforming to IEC 60947-2
5 kA at 250 V DC conforming to IEC 60947-2
50 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2Suitability for isolation Yes conforming to IEC 60947-2 Utilisation category Category A Trip unit name TM-D Trip unit technology Thermal-magnetic Trip unit rating 30 A at 50 °C Protection type Overload protection
Short-circuit protectionPollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary
Control type Toggle Mounting mode Fixed Mounting support Backplate Upside connection Front downside connection Front Mechanical durability 13000 cycles Electrical durability Category A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 Connection pitch 25 mm local signalling Positive contact indication Neutral protection setting Without protection Earth-leakage protection Without Height 130 mm Width 75 mm Depth 60 mm Environment
Standards JIS C8201-2-2
EN/IEC 60947-1
GB/T 14048.2
EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529 IK degree of protection IK07 conforming to IEC 62262 Ambient air temperature for operation -25…70 °C Ambient air temperature for storage -35…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 9.5 cm Package 1 Width 8.5 cm Package 1 Length 14 cm Package 1 Weight 790 g Unit Type of Package 2 S02 Number of Units in Package 2 12 Package 2 Height 15 cm Package 2 Width 30 cm Package 2 Length 40 cm Package 2 Weight 9.935 kg Unit Type of Package 3 P12 Number of Units in Package 3 384 Package 3 Height 75 cm Package 3 Width 80 cm Package 3 Length 120 cm Package 3 Weight 328 kg Contractual warranty Warranty 18 months