G20F3A200
G20F3A200 - SCHNEIDER
Circuit breaker, GoPact MCCB 200, 3 poles, 36kA at 415VAC, 200A rating, TMD trip unit, adjustable thermal protection
IN STOCK
Description
This product is part of the new GoPact Molded Case Circuit Breakers range (MCCB). It is a complete 3 poles circuit breaker made of a 200A breaker frame and of a thermal magnetic trip unit (TMD). GoPact MCCB has a good price-performance ratio for basic applications and delivers a reliable electrical protection for your applications. The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz. The operational voltage is 415VAC 50/60Hz. This product embeds a 200A rating (In) thermal-magnetic trip unit (TMD). This TMD trip unit provides an adjustable thermal protection Ir (against overloads) with a setting range from 0.7xIn to 1xIn (140A-200A). And it provides a fixed magnetic (against short-circuits) protection set to 12xIn (2400A). GoPact MCCB comes with a variety of optional accessories simple to choose and to install. Product dimensions are 75mm (Width) x 130mm (Height) x 60mm (Depth). The weight is 0.9 kg. GoPact MCCB 200 is IEC 60947-1 and IEC 60947-2 certified. GoPact MCCB range benefits from Schneider Electric quality assurance.
Specifications
Main Range of product GoPact MCCB product or component type Circuit breaker Product name GoPact MCCB 200 Device application Distribution poles description 3P Protected poles description 3D [In] rated current 200 A at 40 °C [Ue] rated operational voltage 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 Suitability for isolation Yes conforming to EN/IEC 60947-2 Utilisation category Category A [Icu] rated ultimate short-circuit breaking capacity 36 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2Performance level F 36 kA 380/415 V AC Trip unit name TM-D Trip unit technology Thermal-magnetic Trip unit protection functions LI Control type Toggle Circuit breaker mounting mode Fixed Complementary [Ui] rated insulation voltage 440 V AC conforming to EN/IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2 [Ics] rated service short-circuit breaking capacity 36 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2Mechanical durability 20000 cycles Electrical durability 6000 cycles at 415 V In Power dissipation per pole 24 W mounting support Backplate Mounting position Horizontal and vertical
Flat on the backUpside connection Front downside connection Front Connection terminals Screw terminals Connection pitch 25 mm Protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)Trip unit rating 200 A at 40 °C Long-time pick-up adjustment type Ir (thermal protection) Adjustable [Ir] long-time protection pick-up adjustment range 0.7...1 x In Long-time protection delay adjustment type tr Fixed Instantaneous protection pick-up adjustment type Ii Fixed [Ii] instantaneous protection pick-up adjustment range 12 x In Width (W) 75 mm Height (H) 130 mm Depth (D) 60 mm net weight 0.9 kg Colour Grey (RAL 7035) Environment Standards EN/IEC 60947-1
EN/IEC 60947-2
EN/IEC 60947-2 Annex HOvervoltage category III Pollution degree 3 conforming to IEC 60664-1 IP degree of protection IP20 conforming to IEC 60529 Ambient air temperature for operation -20…55 °C ambient air temperature for storage -35…85 °C Operating altitude 0...2000 m without derating
2000...5000 m with derating