GV2P08 - scheinder
TeSys GV2 - Circuit breaker - thermal magnet - 2.5…4 A - screw clamp terminals
stock:885description
Provides connection with screw clamp terminals Provides start-stop control with 100 000 cycle AC-3 guaranteed router control button Certified to multi standards (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
- New modern look and feel of all machines
- Wide range of GVs: Magnetic, thermal magnetic, different sizes (GV2,GV3,GV4)
- Easier to install and operate with multi-standard screws
- Safe and long-lasting power connection with EverLink terminals
- Digital customer experience for technical documentation
- Environmental performance of the product
Specifications Main
main
sherry TeSys Deca Name of the product TeSys GV2
TeSys DecaProduct or component type Engine circuit breaker Product group GV2P device application Engine protection trip unit technology Thermal Magnetic Complement
pole definition 3P Network type HUNGRY usage category Category A conforming
to IEC 60947-2 AC-3 conforming to IEC 60947-4-1
AC-3e conforming to IEC 60947-4-1network frequency 50/60 Hz conforming to IEC 60947-4-1 fixing mode 35 mm symmetrical DIN rail: with clip
Panel: with screws (with 2 x M4 screws)engine power kW 1.1 kW at 400/415 V AC 50/60 Hz
1.5 kW at 500 V AC 50/60 Hz
2.2 kW at 690 V AC 50/60 Hzbreaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/ 60 Hz conforming to IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service short-circuit breaking capacity 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2Control type Rotary arm [In] rated current 4A thermal protection adjustment range 2.5…4 A conforming to IEC 60947-4-1 magnetic tripping current 51A [Ith] classic open air thermal current 4 A conforming to IEC 60947-4-1 [Ue] nominal operating voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Ui] nominal insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] nominal impulse withstand voltage 6 kV conforming to IEC 60947-2 phase failure sensitivity Yes conforming to IEC 60947-4-1 suitability for insulation Yes conforming to IEC 60947-1 § 7-1-6 power dissipation per pole 2.5W Mechanical durability 100000 cycles electrical durability 100000 cycles for AC-3 at 415 V In
100000 cycles for AC-3e at 415 V Innominal duty Continuous conforming to IEC 60947-4-1 tightening torque 1.7 Nm - on screw clamp terminal Width 45mm Height 89mm Depth 97mm colour Dark grey Environment
standards EN/IEC 60947-2
EN/IEC 60947-4-1Product certifications CCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCAHR protection degree IK04 IP protection degree IP20 conforming to IEC 60529 climatic resistance Conforming to IACS E10 Storage environmental conditions -40…80 °C fire resistance 960 °C conforming to IEC 60695-2-11 ambient air temperature for operation -20…60 °C mechanical durability Shocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 Hzworking height 2000m Packaging units
Unit Type of Package 1 P.C.E. Number of Units in Package 1 One Package 1 Height 4,800cm Package 1 Width 9,500cm Package 1 Length 10,200cm Package 1 Weight 324,000g Unit Type of Package 2 S02 Number of Units in Package 2 20 Package 2 Height 15,000cm Package 2 Width 30,000cm Package 2 Length 40,000cm Package 2 Weight 6,756kg Unit Type of Package 3 P06 Number of Units in Package 3 320 Package 3 Height 75,000cm Package 3 Width 60,000cm Package 3 Length 80,000cm Package 3 Weight 114,912kg