GZ1E20
GZ1E20 - SCHNEIDER
Motor circuit breaker,Easy TeSys Power,GZ1E,AC-3,3P,13..18A,thermal magnetic trip
In Stock
Description
GZ1 E are 3-pole 3d thermal magnetic circuit breakers specially designed for the control and protection of motors in accordance with IEC 60947-2 and IEC 60947-4-1 standards. Setting range of thermal trips is 13-18A with thermomagnetic trip unit, IP 41 in GV2 MC01 box and provides IP 55 protection in the GV2 MC02 box 0.1 M-loop electrical/mechanical durability provides standard reliability and durability These circuit breakers are designed for connection with screw clamp terminals Available worldwide, multi-standard certified (IEC, UL, CSA, CCC, EAC, Marine ) and Green Premium compliant (RoHS/REACh) Available worldwide, multi-standard certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHS/REACh)
Specifications
Range Easy TeSys Range of product Easy TeSys Power product or component type Circuit breaker Device short name GZ1E Device application Motor Trip unit technology Thermal-magnetic Suitability for isolation Yes conforming to IEC 60947-1 appendix 7.1.6 Colour Grey (RAL 7011) Complementary
Poles description 3P Network type AC Utilisation category AC-3 Network frequency 50/60 Hz conforming to IEC 60947-2 Mounting mode By clips
By screwsMounting support Rail Mounting position Any position Motor power kW 4 kW at 230 V AC 50/60 Hz
7.5 kW at 400 V AC 50/60 Hz
9 kW at 440 V AC 50/60 Hz
10 kW at 500 V AC 50/60 Hz
15 kW at 690 V AC 50/60 HzBreaking capacity Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 2 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 10 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 6 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service short-circuit breaking capacity 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2Control type Push-button Thermal protection adjustment range 13…18 A Magnetic tripping current 223 A [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2 Power dissipation 2.5 W (per pole) Mechanical durability 100000 cycles Electrical durability 100000 cycles for AC-3 Maximum operating rate 25 cyc/h Connections - terminals Screw clamp terminals 2 1…6 mm² - cable stiffness: solid
Screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible without cable end
Screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable endHeight 89 mm Width 44.5 mm Depth 78 mm net weight 0.26 kg Environmental
Standards IEC 60947-2
IEC 60947-4Protective treatment TH IP degree of protection IP20 conforming to IEC 60529 Ambient air temperature for operation -20…60 °C ambient air temperature for storage -40…80 °C Fire resistance 960 °C conforming to IEC 60695-2-1 Operating altitude 2000 m