LC1E1801M5
LC1E1801M5 - SCHNEIDER
Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3,<=440V,18A,220V AC coil,50Hz,1NC auxiliary contact
In Stock
Description
EasyPact TVS contactor for motor applications up to 18A 9kW@440V 220V 50Hz AC coil, 1NC internal auxiliary contacts, provides power and control connections with screw clamps 45 mm wide for standard operating speeds up to 1800 RPM 1.2 M Cycles electrical endurance AC- 3 and 10 M-loops provide standard reliability and durability with mechanical durability Can cover -5°C to 55°C operating temperature and DIN rail mounted, no derating up to 3000m altitude Multi standard certified (IEC, CCC, EAC) and Green Premium compliant ( RoHs/Reach) Multi standard certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach)
Specifications
Range Easy TeSys Range of product Easy TeSys Control product or component type Contactor Device short name LC1E contactor application Resistive load
Motor controlUtilisation category AC-1
AC-3Poles description 3P [Ue] rated operational voltage Power circuit: <= 690 V AC 50/60 Hz [Ie] rated operational current 32 A (at <55 °C) at <= 415 V AC AC-1 for power circuit
18 A (at <55 °C) at <= 440 V AC AC-3 for power circuit[Uc] control circuit voltage 220 V AC 50 Hz Complementary
Motor power kW 4 kW at 220...230 V AC 50/60 Hz
7.5 kW at 380...400 V
9 kW at 415 V
9 kW at 440 V
10 kW at 500 V
10 kW at 660...690 VPole contact composition 3 NO [Ith] conventional free air thermal current 32 A (at 55 °C) Irms rated making capacity 180 A at 440 V AC for power circuit conforming to IEC 60947-4-1 Rated breaking capacity 144 A at 440 V for power circuit conforming to IEC 60947 [Icw] rated short-time withstand current 145 A 40 °C - 10 s for power circuit
84 A 40 °C - 60 s for power circuit
40 A 40 °C - 600 s for power circuitAssociated fuse rating 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
35 A gG at <= 690 V coordination type 1 for power circuitAverage impedance 2.5 mOhm - Ith 32 A 50 Hz for power circuit Power dissipation per pole 0.81 W AC-3
2.6 W AC-1[Ui] rated insulation voltage 690 V conforming to IEC 60947-4-1 Overvoltage category III Pollution degree 3 [Uimp] rated impulse withstand voltage 6 kV coil not connected to the power circuit conforming to IEC 60947 Mechanical durability 10000000 cycles Electrical durability 300000 cycles AC-1
1200000 cycles AC-3Control circuit type AC at 50 Hz Control circuit voltage limits Environmental
Standards IEC 60947-5-1
IEC 60947-4-1
IEC 60947-1Product certifications EAC
CEIP degree of protection IP2X conforming to IEC 60529 Protective treatment TH (pollution degree 3) conforming to IEC 60068-2-30 test Db Permissible ambient air temperature around the device -20…70 °C at Uc
-60…80 °C storage
-5…55 °C operationOperating altitude 3000 m without derating Fire resistance 850 °C conforming to IEC 60695-2-1 Mechanical robustness Vibrations contactor open (1.5 Gn, 5...300 Hz)
Vibrations contactor closed (3 Gn, 5...300 Hz)
Shocks contactor open (7 Gn for 11 ms)
Shocks contactor closed (10 Gn for 11 ms)Height 74 mm Width 45 mm Depth 80 mm net weight 0.3 kg