top of page
LC1K0610B7

LC1K0610B7

SKU: TR
$11.44Price

LC1K0610B7 - schneider

TeSys K contactor - 3P(3 NO) - AC-3 - <= 440 V 6 A - 24 V AC coil

stock : 50

description

Provides reliability and durability for standard applications up to 600 rpm and environments up to 50°C Very compact (45 mm wide), DIN rail mounting or screw fixing Multi standard certified (IEC, UL, CSA, CCC) , EAC), Green Premium compliant (RoHS/REACh).

  • Specifications Main

    Main

    Sherry TeSys
    Product or Component Type Contactor
    Product Group LC1K
    Device Application Control
    contactor application Engine control

    Complement

    usage category AC-3
    AC-3e
    AC-4
    Definition of Pole 3P
    power pole contact composition 3 NA
    [Ue] nominal operating voltage Power circuit: <= 690 V AC <= 400 Hz
    Signaling circuit: <= 690 V AC <= 400 Hz
    [Ie] rated operating current 6 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
    6 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
    control circuit type AC at 50/60 Hz
    control circuit voltage 24V AC 50/60Hz
    engine power kW 1.5 kW at 220...230 V AC 50/60 Hz AC-3
    2.2 kW at 380...415 V AC 50/60 Hz AC-3
    3 kW at 440/690 V AC 50 /60 Hz AC-3
    1.5 kW at 220...230 V AC 50/60 Hz AC-3e
    2.2 kW at 380...415 V AC 50/60 Hz AC-3e
    3 kW at 440/690 V AC 50/60 Hz AC-3e
    1.5 kW at 220...230 V AC 50 /60 Hz AC-4
    2.2 kW at 380...415 V AC 50/60 Hz AC-4
    3 kW at 440/690 V AC 50/60 Hz AC-4
    auxiliary contact arrangement 1 NA
    [Uimp] rated impact withstand voltage? 8 kV
    overvoltage category III
    [Ith] classical open air thermal current 20 A (at 60 °C) for power circuit
    10 A (at 50 °C) for signaling circuit
    Irms nominal closing capacity 110 A AC for power circuit conforming to IEC 60947
    110 A AC for signaling circuit conforming to IEC 60947
    rated breaking capacity 110 A at 220...230 V
    conforming to
    IEC
    60947
    to IEC 60947
    70 A at 660...690 V conforming to IEC 60947
    [Icw] rated short-time withstand current 90 A 50 °C - 1 s for power circuit
    85 A 50 °C - 5 s for power circuit
    80 A 50 °C - 10 s for power circuit
    60 A 50 °C - 30 s for power circuit
    45 A 50 °C - 1 min for power circuit
    40 A 50 °C - 3 min for power circuit
    20 A 50 °C - >= 15 min for power circuit
    80 A - 1 s for signalling circuit
    90 A - 500 ms for signalling circuit
    110 A - 100 ms for signalling circuit
    relevant insurance value 25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
    average impedance 3 mOhm - Ith 20 A 50 Hz for power circuit
    [Ui] nominal insulation voltage Power circuit: 600 V conforming to UL 508
    Power circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-5-1
    Signalling circuit: 600 V conforming to UL 508
    Power circuit: 600 V conforming to CSA C22.2 No 14
    Signalling circuit: 600 V conforming to CSA C22.2 No 14
    insulation resistance > 10 MOhm for signaling circuit
    Take-off power in VA 30 VA (at 20 °C)
    Holding power consumption in VA 4.5 VA (at 20 °C)
    heat distribution 1.3W
    control circuit voltage limits Working: 0.8...1.15 Uc (at <50 °C)
    Drop: >= 0.20 Uc (at <50 °C)
    connections - terminals Screw clamp terminals 1 wire(s) 1.5…4 mm²solid?
    Screw clamp terminals 1 wire(s) 0.75…4 mm²flexible without cable end
    Screw clamp terminals 1 wire(s) 0.34…2.5 mm²flexible with
    Screw clamp terminals 2 wire(s) 1.5…4 mm²solid?
    Screw clamp terminals 2 wire(s) 0.75…4 mm²flexible without cable end
    Screw clamp terminals 2 wire(s) 0.34…1.5 mm²flexible with
  • Additional Product Information

    Maximum operating speed 3600 cyc/h
    auxiliary contact type type instant 1 NA
    signaling circuit frequency <= 400Hz
    minimum switching current 5 mA for signaling circuit
    minimum switching voltage 17 V for signaling circuit
    Mounting Support Rail
    Plate
    tightening torque 1.3 Nm - on screw clamp terminals - with screwdriver Philips No 2
    1.3 Nm - on screw clamp terminals - with screwdriver flat Ø 6 mm
    1.3 Nm - on lug-ring terminals - with screwdriver Pozidriv No 2
    Working hours 10...20 msec coil de-energization and NO opening
    10...20 msec coil energization and NO closing
    security reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
    non-overlap distance 0.5mm
    Mechanical durability 10 Mcycles
    electrical resistance 1.3 Mcycles 6 A AC-3 at Ue <= 440 V
    1.3 Mcycles 6 A AC-3e at Ue <= 440 V
    0.05 Mcycles 36 A AC-4 at Ue <= 440 V
    mechanical strength Arrows Contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Arrows Contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC
    60068-2-27 Arrows Contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
    Arrows Contactor open, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
    Arrows Contactor open, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Arrows Contactor open, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
    Height 58mm
    Width 45mm
    depth 57mm
    Product Weight 0.18 kg
  • Environment and Packing Units

    Environment

    standards EN/IEC 60947-4-1
    GB/T 14048.4
    UL 60947-4-1
    CSA C22.2 No 60947-4-1
    JIS C8201-4-1
    IEC 60335-1:Clause 30.2
    IEC 60335-2-40: Annex JJ
    UL 60335-2-40:Annex JJ
    Product Certificates CB ?diagram?
    CCC
    UL
    CSA
    EAC
    CE
    UKCA
    IP protection degree IP2X compliant with VDE 0106
    preventive maintenance TC conforming to IEC 60068
    TC conforming to DIN 50016
    Storage Environmental Conditions -50…80 °C
    working height Without 2000m
    Flame retardant V1 conforming to UL 94
    Requirement 2 conforming
    to NF F 16-101 Requirement 2 conforming to NF F 16-102

    Packaging units

    Unit Type of Package 1 PCE
    Number of Units in Package 1 1
    Package 1 Height 6,600 cm
    Package 1 Width 4,800 cm
    Package 1 Length 6,200 cm
    Package 1 Weight 178,000g
    Unit Type of Package 2 S02
    Number of Units in Package 2 50
    Package 2 Height 15,000 cm
    Package 2 Width 30,000 cm
    Package 2 Length 40,000 cm
    Package 2 Weight 9,274 kg
    Unit Type of Package 3 P06
    Number of Units in Package 3 400
    Package 3 Height 45,000 cm
    Package 3 Width 60,000 cm
    Package 3 Length 80,000 cm
    Package 3 Weight 83,340 kg
  • properties

    TeSys K contactor - 3P(3 NO) - AC-3 - <= 440 V 6 A - 24 V AC coil

    LC1K0610B7

    TeSys K is a compact contactor series with a wide range of coil voltages and terminal connection options.
    notification_ok
    The offer includes special versions for railway (TeSys S207) and electric home (TeSys S335) applications.
    One of the smallest contactor offerings on the market.
    The series offers powerful performance for its compact size and promises seamless integration in all applications.
    It is widely used for industrial, infrastructure and building applications.
No Reviews YetShare your thoughts. Be the first to leave a review.
bottom of page