LC1K0610F7
LC1K0610F7 - schneider
Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 6A, 1 NO aux., 110VAC coil
stock: 15
Description
LC1K0610F7 is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 6A AC-3 2.2kW@400V, it includes a 110V 50/60Hz AC coil and 1NO auxiliary contact. LC1K0610F7 is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 2.2kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it includes a 110V 50/60Hz AC coil and 1NO built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Provides a control circuit compatible with 50Hz and 60Hz supplies and 1NO built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).
Specifications Main
Main Range TeSys Product or Component Type Contactor Device short name LC1K Device Application Control Contactor application Motor control Complementary Utilisation category AC-3
AC-3e
AC-4Poles description 3P power pole contact composition 3 NO [Ue] rated operational voltage Power circuit <= 690 V AC <= 400 Hz
Signalling circuit <= 690 V AC <= 400 Hz[Ie] rated operational current 6 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
6 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuitControl circuit type AC 50/60 Hz [Uc] control circuit voltage 110 V AC 50/60 Hz Motor power kW 1.5 kW 220...230 V AC 50/60 Hz AC-3
2.2 kW 380...415 V AC 50/60 Hz AC-3
3 kW 440/690 V AC 50/60 Hz AC-3
1.5 kW 220...230 V AC 50/60 Hz AC-3e
2.2 kW 380...415 V AC 50/60 Hz AC-3e
3 kW 440/690 V AC 50/60 Hz AC-3e
1.5 kW 220...230 V AC 50/60 Hz AC-4
2.2 kW 380...415 V AC 50/60 Hz AC-4
3 kW 440/690 V AC 50/60 Hz AC-4Auxiliary contact composition 1 NO [Uimp] rated impulse withstand voltage 8 kV Overvoltage category III [Ith] conventional free air thermal current 20 A (at 140 °F (60 °C)) for power circuit
10 A (at 122 °F (50 °C)) for signalling circuitIrms rated making capacity 110 A AC for power circuit conforming to IEC 60947
110 A AC for signalling circuit conforming to IEC 60947Rated breaking capacity 110 A at 220...230 V conforming to IEC 60947
110 A at 380...400 V conforming to IEC 60947
110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947[Icw] rated short-time withstand current 90 A 122 °F (50 °C) - 1 s for power circuit
85 A 122 °F (50 °C) - 5 s for power circuit
80 A 122 °F (50 °C) - 10 s for power circuit
60 A 122 °F (50 °C) - 30 s for power circuit
45 A 122 °F (50 °C) - 1 min for power circuit
40 A 122 °F (50 °C) - 3 min for power circuit
20 A 122 °F (50 °C) - >= 15 min for power circuit
80 A - 1 s for signalling circuit
90 A - 500 ms for signalling circuit
110 A - 100 ms for signalling circuitAssociated fuse rating 25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660Average impedance 3 mOhm - Ith 20 A 50 Hz for power circuit [Ui] rated insulation voltage Power circuit 600 V UL 508
Power circuit 690 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-5-1
Signalling circuit 600 V UL 508
Power circuit 600 V CSA C22.2 No 14
Signalling circuit 600 V CSA C22.2 No 14Insulation resistance > 10 MOhm for signalling circuit Inrush power in VA 30 VA (at 68 °F (20 °C)) Hold-in power consumption in VA 4.5 VA (at 68 °F (20 °C)) Heat dissipation 1.3 W Control circuit voltage limits Operational: 0.8...1.15 Uc (at <122 °F (50 °C))
Drop-out: >= 0.20 Uc (at <122 °F (50 °C))Connections - terminals screw clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid
screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end
screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end
screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid
screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end
screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable endMaximum operating rate 3600 cyc/h Auxiliary contacts type Instantaneous 1 NO Signalling circuit frequency <= 400 Hz Minimum switching current 5 mA for signalling circuit Minimum switching voltage 17 V for signalling circuit Mounting Support Plate
RailTightening torque 7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals Philips No 2
7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals flat Ø 6 mm
7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals pozidriv No 2Operating time 10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closingSafety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1Non overlap distance 0.02 in (0.5 mm) Mechanical durability 10 Mcycles Electrical durability 1.3 Mcycles 6 A AC-3 <= 440 V
1.3 Mcycles 6 A AC-3e <= 440 V
0.05 Mcycles 36 A AC-4 <= 440 VMechanical robustness Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6Height 2.3 in (58 mm) Width 1.8 in (45 mm) Depth 2.2 in (57 mm) Net Weight 0.40 lb(US) (0.18 kg) Environment and Packing Units
Environment Standards EN/IEC 60947-4-1
GB/T 14048.4
UL 60947-4-1
CSA C22.2 No 60947-4-1
JIS C8201-4-1
IEC 60335-1:Clause 30.2
IEC 60335-2-40:Annex JJ
UL 60335-2-40:Annex JJProduct Certifications CB Scheme
CCC
UL
CSA
EAC
CE
UKCAIP degree of protection IP2X VDE 0106 Protective treatment TC IEC 60068
TC DIN 50016Ambient Air Temperature for Storage -58…176 °F (-50…80 °C) Operating altitude