top of page
LV431631

LV431631

SKU: 101
$912.00 Regular Price
$820.80Sale Price

LV431631SCHNEIDER

 

Circuit breaker, ComPact NSX250F, 36kA/415VAC, TMD trip unit 200A, 3 poles 3d

Description

This Compact NSX250F is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 200A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX250F is part of Schneider Electric EcoStruxure Power architecture.

  • Specifications Main

    Main
    Range ComPact
    Product name ComPact NSX
    Range of product ComPact NSX100...250
    Device short name NSX250F
    product or component type Circuit breaker
    Device application Distribution
    Number of poles 3P
    Protected poles description 3t
    [In] rated current 200 A at 40 °C
    [Ue] rated operational voltage 690 V AC 50/60 Hz
    Network type AC
    Network frequency 50/60 Hz
    Suitability for isolation Yes conforming to EN/IEC 60947-2
    Utilisation category Category A
    [Icu] rated ultimate short-circuit breaking capacity 85 kA at 240 V AC 50/60 Hz conforming to UL 508
    22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
    35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    35 kA at 480 V AC 50/60 Hz conforming to UL 508
    30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
    15 kA at 600 V AC 50/60 Hz conforming to UL 508
    Performance level F 36 kA 415 V AC
    Trip unit name TM-D
    Trip unit technology Thermal-magnetic
    Trip unit protection functions LI
    Control type Toggle
    Circuit breaker mounting mode Fixed
    Complementary
    [Ui] rated insulation voltage 800 V AC 50/60 Hz
    [Uimp] rated impulse withstand voltage 8 kV
    [Ics] rated service short-circuit breaking capacity 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
    30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
    8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    Mechanical durability 20000 cycles
    Electrical durability 5000 cycles at 690 V In
    10000 cycles at 690 V In/2
    10000 cycles at 440 V In
    20000 cycles at 440 V In/2
    Mounting support Backplate
    Upside connection Front
    downside connection Front
    Connection pitch 35 mm
    Protection type L : for overload protection (thermal)
    I : for short-circuit protection (magnetic)
    Trip unit rating 200 A at 40 °C
    Long-time pick-up adjustment type Ir (thermal protection) Adjustable
    [Ir] long-time protection pick-up adjustment range 0.7...1 x In
    Long-time protection delay adjustment type tr Fixed
    [tr] long-time protection delay adjustment range 120…400 s at 1.5 x In
    15 s at 6 x Ir
    Short-time protection pick-up adjustment type Isd Adjustable
    [Isd] Short-time protection pick-up adjustment range 5...10 x In
    Short-time protection delay adjustment type tsd Fixed
    earth-leakage protection Without
    Number of slots for electrical auxiliaries 5 slot(s)
    Width (W) 105 mm
    Height (H) 161 mm
    Depth (D) 86 mm
    net weight 2.4 kg
  • Environment

    Environment
    Standards EN/IEC 60947
    Product certifications Marine
    CCC
    EAC
    Overvoltage category Class II
    Electrical shock protection class Class II
    Pollution degree 3 conforming to IEC 60664-1
    IP degree of protection IP40 conforming to IEC 60529
    IK degree of protection IK07 conforming to IEC 62262
    Ambient air temperature for operation -25…70 °C
    ambient air temperature for storage -50…85 °C
    Relative humidity 0…95 %
    Operating altitude 0...2000 m without derating
    2000 m...5000 m with derating
    Packing Units
    Unit Type of Package 1 PCE
    Number of Units in Package 1 1
    Package 1 Height 14 cm
    Package 1 Width 11.5 cm
    Package 1 Length 19 cm
    Package 1 Weight 2.003 kg
    Unit Type of Package 2 S04
    Number of Units in Package 2 12
    Package 2 Height 30 cm
    Package 2 Width 40 cm
    Package 2 Length 60 cm
    Package 2 Weight 24.802 kg
No Reviews YetShare your thoughts. Be the first to leave a review.
bottom of page