RM17TG20 - SCHNEIDER

phase control relay RM17-T - range 183..484 V AC

In Stock

Explanation

Applicable to a wide range of industrial automation applications such as lifting, packaging, hoists, textile, water It has one of the slimmest form-factors on the market with a width of 17.5mm and allows flexible and easy installation on a DIN rail using the same space as any modular 1-pole DIN device It is also sealable a cover offers simple and precise adjustments with screw cutters The product monitors its own power supply, the output relay is de-energized when the power supply is abnormal Multi-function controller for a wide choice of hardware-integrated logical automatic systems, ideal for retrofitting old installations without the use of PLC.

 

Only 5 left in stock
  • Specifications

    Product series Harmony Control Relays
    relay type Control relay
    Product or component type 3 phase control relay
    product specific application For 3 phase supply
    relay name RM17TG
    Parameters monitored by the relay Phase sequence
    Phase failure detection (2 or more phase interruptions)
    delay time Without
    Switching capacity in VA 1250VA
    measuring range 208...480V AC
    contact type and arrangement 2 K/A
    Control circuit voltage (Uc) 208...440V
  • Complementary

    maximum switching voltage 250V AC
    250V DC
    minimum switching current 10 mA at 5 V DC
    [Un] rated nominal voltage Self-powered
    supply voltage limits 183…484V AC
    control circuit voltage limits - 12% + 10% Flour
    Power consumption in VA 0…22 VA at 400 V AC 50 Hz
    voltage detection threshold < 100V AC
    control circuit frequency 50...60 Hz +/- 10%
    output contacts 2 K/A
    rated output current 5 a
    measuring voltage limits 183…484V AC
    Delay when power on 650ms
    voltage range 183...484V
    response time <= 130 ms (in case of an error)
    Marking CE
    overvoltage category III conforming to IEC 60664-1
    insulation resistance > 500 MOhm at 500 V DC conforming to IEC 60255-5
    > 500 MOhm at 500 V DC conforming to IEC 60664-1
    [Ui] nominal insulation voltage 400 V conforming to IEC 60664-1
    supply frequency 50/60 Hz +/- 10%
    working position Without any location
    connections - terminals Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) without solid cable end
    Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20... AWG 14) solid without cable end
    Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible Screw
    terminals with cable end, 2 x 0.2...2 x 1, 5 mm² (AWG 24...AWG 16) flexible Cable end
    tightening torque 0.6…1 Nm conforming to IEC 60947-1
    enclosure material Self-extinguishing plastic
    local signaling Relay ON: LED (yellow)
    mounting support 35 mm symmetrical DIN rail conforming to IEC 60715
    electrical durability 10000 cycles
    Mechanical durability 30000000 cycles
    working speed <= 360 operations/hour full load
    usage category Conforming to AC-12IEC 60947-5-1
    Conforming to AC-13IEC 60947-5-1
    Conforming to AC-14IEC 60947-5-1
    Conforming to AC-15IEC 60947-5-1
    Conforming to DC-12IEC 60947-5-1
    DC-13 conforming to IEC 60947-5-1
    security reliability data B10d = 850000
    MTTFd = 924.6 years
    Width 17.5mm
    Product weight 0.13kg
    Control type Without test button
  • Environmental

    electromagnetic compatibility Emission standard for industrial environments conforming to IEC 61000-6-4
    Emission standard for residential, commercial and light industrial environments conforming to IEC 61000-6-3
    Immunity for industrial environments conforming to IEC 61000-6-2
    standards IEC 60255-1
    Product certifications GOST
    C-Tick
    UL
    CSA
    GL
    directives 73/23/EEC - low voltage directive
    89/336/EEC - electromagnetic compatibility
    Storage environmental conditions -40…70 °C
    ambient air temperature for operation -20…50 °C
    relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
    vibration resistance 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6
    1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
    impact resistance 11 ms for 15 gn conforming to IEC 60255-21-1
    IP protection degree IP20 conforming to IEC 60529 (terminals)
    IP30 conforming to IEC 60529 (enclosure)
    degree of contamination 3 conforming to IEC 60664-1
    dielectric test voltage 2 kV AC 50 Hz, 1 min
    non-propagating shock wave 4kV
No Reviews YetShare your thoughts. Be the first to leave a review.