top of page
RM35JA32MR

RM35JA32MR

SKU: TR
$72.56Price

RM35JA32MR -  scheinder

Current control relay 0.15A…15A, 2 C/O

stock : 67

description

Applies to a wide range of industrial automation applications such as lifting, packaging, levers, textiles, water One of the mid-form-factors on the market with 35mm width allowing flexible and easy installation on a DIN rail using the same space as any modular 3-pole DIN device Also a diagnostic button , sealable cover, offers simple and precise adjustments with screw cutters Provides the user with automatic shutdown management and fault information for fast fault detection and troubleshooting The multi-function controller for a wide selection of embedded logical automatic systems, ideal for retrofitting old installations without the use of PLC.

  • Specifications Main

    Main
    Range of product Harmony Control Relays
    Relay type Current control relay
    Product or component type Current control relay
    Relay name RM35JA
    Relay monitored parameters Overcurrent or undercurrent in window mode
    Overcurrent or undercurrent detection
    time delay Adjustable 0.1...30 s, +/- 10 % of the full scale value Tt- time delay upon fault
    Switching capacity in VA 2000 VA
    Minimum switching current 10 mA at 5 V DC
    Maximum switching current 8 A AC
    Maximum power consumption in VA 3.5 VA
    Measurement range 150 mA...15 A AC/DC
    Utilisation category AC-15 conforming to IEC 60947-5-1
    DC-13 conforming to IEC 60947-5-1
    AC-1 conforming to IEC 60947-4-1
    DC-1 conforming to IEC 60947-4-1
    Contacts type and composition 2 C/O
    Complementary
    Reset time 1500 ms at maximum voltage
    Maximum switching voltage 250 V AC
    Supply voltage limits 20.4…264 V AC/DC
    operating voltage tolerance - 15 % + 10 % Un
    Maximum power consumption in W 1.5 W DC
    Resistance across terminals 0.005 Ohm at E3-M terminals
    0.015 Ohm at E2-M terminals
    0.05 Ohm at E1-M terminals
    Output contacts 2 C/O
    Nominal output current 8 A
    Maximum measuring cycle 100 ms measurement cycle as true rms value
    Internal input resistance 0.015 Ohm
    0.005 Ohm
    0.05 Ohm
    Setting accuracy of the switching threshold +/- 10 % of the full scale
    Switching threshold drift <= 0.05 % per degree centigrade depending permissible ambient air temperature
    <= 1 % within the supply voltage range
    Setting accuracy of time delay 10 P
    Time delay drift <= 0.05 % per degree centigrade depending permissible ambient air temperature
    <= 1 % within the supply voltage range
    Hysteresis 5…50 % adjustable of threshold setting
    3 % fixed of full scale for window mode
    delay at power up 0.3 s
    Repeat accuracy +/- 0.5 % for input and measurement circuit
    +/- 2 % for time delay
    Measurement error < 1 % over the whole range with voltage variation
    0.05 %/°C with temperature variation
    Response time <= 500 ms (on crossing the threshold)
    Threshold setting 10...100 %
    Overvoltage category III conforming to IEC 60664-1
    III conforming to UL 508
    Insulation resistance > 100 MOhm at 500 V DC conforming to IEC 60255-27
    Insulation Between supply and measurement
    Connections - terminals Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
    Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
    Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
    Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
    Tightening torque 0.6…1 N.m conforming to IEC 60947-1
    Housing material Self-extinguishing plastic
    Local signalling LED (yellow) for relay ON
    LED (green) for power ON
    Mounting support 35 mm DIN rail conforming to IEC 60715
    Electrical durability 100000 cycles
    Mechanical durability 10000000 cycles
    [Un] rated nominal voltage 24...240 V AC/DC 50/60 Hz, non self-powered
    Safety reliability data MTTFd = 296.8 years
    B10d = 270000
    Contacts material Cadmium free
    Width 35 mm
    Control type With test button
    Net weight 0.12 kg
  • Environment

    Immunity to microbreaks 50 ms
    Electromagnetic compatibility Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1
    Immunity for industrial environments conforming to IEC 61000-6-2
    Emission standard for industrial environments conforming to IEC 61000-6-4
    Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
    Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3
    Electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4
    Electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4
    Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5
    Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5
    Conducted and radiated emissions class B group 1 conforming to CISPR 11
    Conducted and radiated emissions class B conforming to CISPR 22
    Emission standard for residential, commercial and light-industrial environments (except radiated emission) conforming to IEC 61000-6-3
    Standards IEC 60255-1
    Product certifications CE
    GL
    CCC
    EAC
    RCM
    UL
    CSA
    Ambient air temperature for storage -40…70 °C
    Ambient air temperature for operation -20…50 °C at 60 Hz
    -20…60 °C at 50 Hz
    Environmental characteristic 3K3 C
    Relative humidity 93…97 % at 25…55 °C conforming to IEC 60068-2-30
    Vibration resistance 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
    1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
    0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
    0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
    Shock resistance 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27
    5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
    IP degree of protection IP20 (terminals) conforming to IEC 60529
    IP50 (front panel) conforming to IEC 60529
    IP30 (housing) conforming to IEC 60529
    Pollution degree 3 conforming to IEC 60664-1
    3 conforming to UL 508
    Dielectric test voltage 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
    Packing Units
    Unit Type of Package 1 PCE
    Number of Units in Package 1 1
    Package 1 Height 7.8 cm
    Package 1 Width 4.5 cm
    Package 1 Length 9.5 cm
    Package 1 Weight 131 g
    Unit Type of Package 2 S02
    Numbe