1SAE341111R0640
1SAE341111R0640 - abb
ESB40-40N-06 Installation Contactor (NO) 40 A - 4 NO - 0 NC - 230 V - Control Circuit 400 Hz
in stock
description
General information
Extended Product Type:ESB20-11N-06
Product ID:1SBE121111R0611
EAN:3471523007499
Catalogue Description:ESB20-11N-06 Installation Contactor
Long Description:ESB20..N installation contactors are used to control single loads up to 20 A and can be operated with AC or DC voltages.
These contactors are intended for use in industrial as well as domestic environments.
The following benefits are achieved:
Hum-free operation, low power consumption and integrated surge protection.
Various contact combinations and accessories are available.
Categories
Products » Low Voltage Products & Systems » Control Products » Contactors » Installation Contactors
Products » Low Voltage Products & Systems » Modular DIN Rail Products » Modular DIN Rail Components MDRC » Mounting Contactors
ESB20-11N-06 - image 0
Order
Package Level 1 EAN:3471523005389
Minimum order quantity:1 piece
Customs Tariff number:85365080
Popular downloads
Technical Data Sheet:2CDC103036C0201
Instructions & Manuals:2CDC103043M6801
Dimensions
Product Net Width:18 mm
Product Net Height:86 mm
Product Net Depth/Length:65 mm
Product net weight:0.14 kg
Technical
Rated Operating Voltage:Main Circuit 220 V DC
Main Circuit 250 V AC
Nominal control circuit voltage (U c ):230 V
Rated Frequency (f):Control Circuit DC
Control Circuit 50 Hz
Control Circuit 60 Hz
Control Circuit 400 Hz
Main Circuit DC
Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Operating Current AC-1 (I e ):(NC) 20 A
(NO) 20 A
Rated Operating Current AC-3 (I e ):(230 V) Single Phase, NC 9 A
(230 V) Single Phase, NO 9 A
Rated Operating Power AC-1 (P e ):(230 V) Single Phase, NC 4.6 kW
(230 V) Single Phase, 4.6 kW NO
Rated Operating Power AC-3 (P e ):(230 V) Single Phase, NC 1.3 kW
(230 V) Single Phase, NO 1.3 kW
Rated Operating Current AC-7a (I e ):(NC) 20 A
(NO) 20 A
Rated Operating Power AC-7a (P e ):(230 V) Single Phase, NC 4.6 kW
(230 V) Single Phase, 4.6 kW NO
Rated Operational Current AC-7b (I e ):(230 V) Single Phase, NC 9 A
(230 V) Single Phase, NO 9 A
Rated Operational Power AC-7b (P e ):(230 V) Single Phase, NC 1.3 kW
(230 V) Single Phase, NO 1.3 kW
Recommended Screw Driver :Control Circuit Pozidriv 1
Main Circuit Pozidriv 1
Rated Impulse Withstand Voltage (U imp ):6 kV
Rated Insulation Voltage (U i ):acc. IEC 60947-4-1 and VDE 0110 (Gr. C) up to 400 V
Connection Capacity Main Circuit:Ferrule 1x 1 ... 6 mm²
Flexible Flexible 2x 1 ... 2.5 mm²
Insulated Flexible 1x 1 ... 6 mm²
Insulated Insulated Flexible 2x 1 ... 1.5 mm²
Flexible 1x 1 ... 6 mm²
Flexible 2x 1 ... 4 mm²
Rigid 1x 1 ... 10 mm²
Rigid 2x 1 ... 4 mm²
Connection of Capacity Control Circuit:Ferrule 1x 1 ... 2.5 mm²
Flexible Flexible 2x 0.75 ... 1.5 mm²
Insulated Insulated 1x 1 ... 2.5 mm²
Insulated Insulated Flexible 2x 0.75 ... 1 mm²
Flexible 1x 1 ... 2.5 mm²
Flexible 2x 1 ... 1.5 mm²
Rigid 1x 0.5 ... 4 mm²
Rigid 2x 0.75 ... 2.5 mm²
Tightening Torque:Control Circuit 0.9 N m
Main Circuit 1.2 N m
Wire Stripping Length:Control Circuit 7 mm
Main Circuit 10 mm
Degree of Protection:IP20
Electrical durability:AC-1 (NO) 150000 cycles
AC-3 (NO) 150000 cycles
AC-7a (NO) 150000 cycles
AC-7b (NO) 150000 cycles
Mechanical durability:1000000 cycles