UA110-30-00RA-80

General Information

  • Extended Product Type:

    UA110-30-00RA-80

  • Product ID:

    1SFL451024R8000

  • EAN:

    7320500260524

  • Catalog Description:

    UA110-30-00RA 220-230V 50Hz Contactor

  • Long Description:

    A 3-phase Contactor suitable for Capacitor switching application. Maximum permissible peak current 100 times the nominal RMS current. Operated with a control voltage, versions from 24…….690 V

  • Popular Downloads

  • Data Sheet, Technical Information:

    1SBC101145L0202

  • Instructions and Manuals:

    5309660-60

  • CAD Dimensional Drawing:

    2CDC001079B0201

  • Dimensions

  • Product Net Width:

    90 mm

  • Product Net Depth / Length:

    155.6 mm

  • Product Net Height:

    170 mm

  • Product Net Weight:

    1.8 kg

  • Technical

  • Number of Main Contacts NO:

    3

  • Number of Main Contacts NC:

    0

  • Number of Auxiliary Contacts NO:

    0

  • Number of Auxiliary Contacts NC:

    0

  • Rated Operational Voltage:

    Main Circuit 1000 V

  • Rated Frequency (f):

    Main Circuit 50 Hz

  • Conventional Free-air Thermal Current (Ith):

    acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 160 A

  • Rated Operational Current AC-1 (Ie):

    (690 V) 40 °C 160 A
    (690 V) 55 °C 145 A
    (690 V) 60 °C 145 A
    (690 V) 70 °C 130 A

  • Rated Operational Current AC-3 (Ie):

    (415 V) 55 °C 110 A
    (440 V) 55 °C 100 A
    (500 V) 55 °C 100 A
    (690 V) 55 °C 82 A
    (1000 V) 55 °C 30 A
    (380 / 400 V) 55 °C 110 A
    (220 / 230 / 240 V) 55 °C 110

  • Rated Operational Power AC-6b (Pe):

    (230 / 240 V) 40 °C, 50 / 60 Hz 45 kvar
    (230 / 240 V) 55 °C, 50 / 60 Hz 40 kvar
    (230 / 240 V) 70 °C, 50 / 60 Hz 35 kvar
    (400 / 415 V) 40 °C, 50 / 60 Hz 80 kvar
    (400 / 415 V) 70 °C, 50 / 60 Hz 60 kvar
    (400 / 415 V) 55 °C, 50 / 60 Hz 70 kvar
    (440 V) 40 °C, 50 / 60 Hz 85 kvar
    (440 V) 55 °C, 50 / 60 Hz 75 kvar
    (440 V) 70 °C, 50 / 60 Hz 70 kvar
    (500 / 550 V), 40 °C, 50 / 60 Hz 95 kvar
    (500 / 550 V) 55 °C, 50 / 60 Hz 82 kvar
    (500 / 550 V) 70 °C, 50 / 60 Hz 78 kvar
    (690 V) 40 °C, 50 / 60 Hz 130 kvar
    (690 V) 55 °C, 50 / 60 Hz 110 kvar
    (690 V) 70 °C, 50 / 60 Hz 100 kvar

  • Rated Breaking Capacity AC-3:

    8 x Ie AC-3

  • Rated Making Capacity AC-3:

    10 x Ie AC-3

  • Maximum Breaking Capacity:

    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A

  • Maximum Electrical Switching Frequency:

    (AC-1) 300 cycles per hour
    (AC-2 / AC-4) 150 cycles per hour
    (AC-3) 300 cycles per hour

  • Rated Insulation Voltage (Ui):

    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
    acc. to UL/CSA 600 V

  • Rated Impulse Withstand Voltage (Uimp):

    Main Circuit 8 kV

  • Mechanical Durability:

    10 million

  • Maximum Mechanical Switching Frequency:

    3600 cycles per hour

  • Coil Operating Limits:

    (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)

  • Rated Control Circuit Voltage (Uc):

    50 Hz 220 ... 230 V
    60 Hz 230 ... 240 V

  • Coil Consumption:

    Holding at Max. Rated Control Circuit Voltage 50 Hz 22 V·A
    Holding at Max. Rated Control Circuit Voltage 60 Hz 26 V·A
    Pull-in at Max. Rated Control Circuit Voltage 50 Hz 350 V·A
    Pull-in at Max. Rated Control Circuit Voltage 60 Hz 450 V·A

  • Operate Time:

    Between Coil De-energization and NC Contact Closing 7 ... 15 ms
    Between Coil Energization and NO Contact Closing 10 ... 25 ms

  • Connecting Capacity Main Circuit:

    Bar 30 mm²
    Flexible with Cable End 1 x 10 ... 70 mm²
    Rigid 2 x 6 ... 65 mm²

  • Connecting Capacity Auxiliary Circuit:

    Flexible with Ferrule 2x 0.75 ... 2.5 mm²
    Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
    Flexible 2x0.75 ... 2.5 mm²
    Solid 2 x 1 ... 4 mm²
    Stranded 1 x 1 .... 4 mm²

  • Degree of Protection:

    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10

  • Connecting Terminals (delivered in open position) Main Poles:

    M8 hexagon socket screw with single connector

  • Terminal Type:

    Cable Clamp

  • Technical UL/CSA

  • Maximum Operating Voltage UL/CSA:

    Main Circuit 600 V

  • Environmental

  • Ambient Air Temperature:

    Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
    Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
    Close to Contactor for Storage -60 ... +80 °C

  • Maximum Operating Altitude Permissible:

    Without Derating 3000 m

  • Resistance to Shock acc. to IEC 60068-2-27:

    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: A 20 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: A 20 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B1 15 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C1 20 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C2 20 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B1 5 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B2 15 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C1 20 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C2 20 g