2834960
REL-IR/LDP-125DC/2X21 - Single relay
2834960 - phoenix
in stock:available
description
Plug-in industrial relay with power contacts, 2 changeover contacts, test button, status LED, freewheeling diode, mechanical switching position indicator, polarity A1+, A2-, input voltage 125 V DC,Product type Single relay,Operating mode : 100% operating factor
Mechanical service life 5x 107 cycles,Insulation: characteristics, Overvoltage category: II
Pollution degree: 2
Electrical connection
Service life electrical see diagram Maximum power dissipation for nominal condition 0.9 W Test voltage (Winding/contact) 2 kV AC (50 Hz, 1 min., winding/contact) Test voltage (Contact/contact) 2 kV AC (50 Hz, 1 min., contact/contact)
connection data
Connection method Plug-in connection inputdata & output data
Nominal input voltage UN 125 V DC Input voltage range 97.5 V DC ... 187.5 V DC Drive and function monostable Typical input current at UN 7.2 mA Typical response time 13 ms Typical release time 14 ms Coil resistance 17380 Ω ±15 % (at 20 °C) output data
Contact switching type2 changeover contactsType of switch contactSingle contactContact materialAgMaximum switching voltage250 V AC/DCMinimum switching voltage5 VLimiting continuous current10 AMaximum inrush current20 A (15 ms)Min. switching current1 mAInterrupting rating (ohmic load) max.2500 VA (for 250 V AC)
Environment & standard
Ambient conditions Degree of protection RT I Ambient temperature (operation) -55 °C ... 70 °C Ambient temperature (storage/transport) -55 °C ... 70 °C standard
Standards/regulations DIN EN 61810-1 VDE 0435-201 EN 50178