2CCS813001R0824
S803B-C100
General Information
Extended Product Type:
S803B-C100
Product ID:
2CCS813001R0824
EAN:
7612271416447
Catalog Description:
S803B-C100 High Performance MCB
Long Description:
The S803B-C100 is a 3-pole High Performance Circuit breaker with C-characteristic, with cage terminal and a rated current of 100 A. It is a current limiting device with a maximum breaking capacity of 16kA at 230/400V. It can be used for voltages up to 230/400V. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S803B-C100 complies with IEC/EN 60947-2 and EN 60898-1 and allows the use for residential, commercial and industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S803B-C100 more comfortable. Due to the fast arc extinction of S803B-C100 your application will be secured.
Technical
Standards:
IEC/EN 60947-2, IEC/EN 60898-1
Tripping Characteristic:
C
Rated Voltage (Ur):
acc. to IEC 60947-2 400 V AC
acc. to IEC 60947-2 225 V DC
acc. to IEC 60898-1 400 V ACRated Operational Voltage:
acc. to IEC 60898-1 400 V
Rated Insulation Voltage (Ui):
acc. to IEC/EN 60664-1 500 V
Rated Impulse Withstand Voltage (Uimp):
6 kV
Input Voltage Type:
AC/DC
Rated Current (In):
100 A
Rated Operational Current (Ie):
100 A
Rated Short-Circuit Capacity:
(230 V) 10 kA
(400 V) 10 kARated Ultimate Short-Circuit Breaking Capacity (Icu):
(230 V) 16 kA
(400 V) 16 kARated Conditional Short-Circuit Current (Inc):
(230 V) 16 kA
(400 V) 16 kARated Service Short-Circuit Breaking Capacity (Ics):
(230 / 400 V AC) 10 kA
Frequency (f):
50...60 Hz
Environmental
Ambient Temperature:
-25...60 °C
Ambient Air Temperature:
Operation -25 … 60 °C
Reference Ambient Air Temperature:
acc. to IEC60947-2 30 °C
Degree of Protection:
IP20
Pollution Degree:
3
RoHS Status:
Following EU Directive 2011/65/EU
RoHS Information:
9AKK107680A3903
2CCC005083D0202Environmental Information:
2CCY413207D0203
Conflict Minerals Reporting Template (CMRT):
9AKK108468A3363
Dimensions
Width in Number of Modular Spacings:
4.5
Product Net Width:
81 mm
Product Net Height:
95 mm
Product Net Depth / Length:
82.5 mm
Product Net Weight:
740 g
Built-In Depth (t2):
82.5 mm
Ordering
Minimum Order Quantity:
1 piece
Package Level 1 Units:
box 1 piece
Package Level 1 Gross Weight:
770 g
Certificates and Declarations
Declaration of Conformity - CE:
2CCC005083D0202
Installation
Instructions and Manuals:
2CCC413016M0008
Popular Downloads
Data Sheet, Technical Information:
2CCC413003C0208
Classifications
ETIM 8:
EC000042 - Miniature circuit breaker (MCB)
ETIM 9:
EC000042 - Miniature circuit breaker (MCB)
WEEE Category:
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B:
Business To Business
CN8:
85362020
eClass:
V11.0 : 27141901
Object Classification Code:
F
Rated Frequency (f):
50/60 Hz
Power Loss:
24 W
at Rated Operating Conditions per Pole 8 WContact Position Indication:
ON / OFF / TRIP
Energy Limiting Class:
3
Number of Poles:
3
Number of Protected Poles:
3
Overvoltage Category:
III
Tightening Torque:
3.5 N·m
Release Type:
C
Actuator Marking:
I / O
Housing Material:
Insulation group I, RAL 7035
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715Mounting Position:
Any
Recommended Screw Driver:
Pozidriv 2
Accessories Available:
Yes
Remarks:
Connection from top and bottom
Connecting with CU only
IP40 in enclosure with cover
Cage terminal with captIIIe screwConnecting Capacity:
Flexible 0 … 50 mm²
Rigid 0 … 70 mm²Terminal Type:
Screw Terminals