top of page
A9D55606

A9D55606

SKU: TR
$31.51Price

A9D55606 - scheinder

Residual current breaker with overcurrent protection (RCBO), Acti9 iDPN N Vigi, 1P+N, 6A, B curve, 6000A, AC type, 30mA

stock: 15

Description

This Acti9 iDPN Vigi is a modular residual current breaker with overcurrent protection (RCBO). It is a 1P+N circuit breaker with 1 protected pole, 6A In rated current and B tripping curve. The earth leakage protection class is AC type with a sensitivity of 30mA. The earth-leakage protection time delay is instantaneous. The Icn rated short circuit breaking capacity is up to 6000A according EN/IEC 61009-2-1 standard. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. Its earth fault indicator on front face allows quick identification of the type of default. A push-test button T is positioned on the front of the device for testing that product is operational. This product is compliant with EN/IEC 61009-2-1 standard. It has an electrical endurance going up to 20000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 220VAC to 240VAC. The Ui rated insulation voltage is 400VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product color is white (RAL9003). The dimensions are (W) 36mm x (H) 85mm x (D) 73mm. The weight is 125g. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is from -5°C to 60°C. The storage temperature is from -40°C to 85°C.

  • Specifications Main

    Main
    Range Acti9
    Product name Acti9 iDPN Vigi
    Product or component type Residual current breaker with overcurrent protection (RCBO)
    Device short name iDPN N Vigi
    Device application Distribution
    Poles description 1P + N
    Number of protected poles 1
    Neutral position Left
    [In] rated current 6 A
    Network type AC
    Trip unit technology Thermal-magnetic
    Curve code B
    Earth-leakage sensitivity 30 mA
    Earth-leakage protection time delay Instantaneous
    Earth-leakage protection class Type AC
    Breaking capacity 6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
    Suitability for isolation Yes conforming to EN/IEC 60947-2
    Complementary
    Complementary Outgoer
    Network frequency 50 Hz
    [Ue] rated operational voltage 230...240 V AC 50 Hz
    Magnetic tripping limit 3...5 x In
    Residual current tripping technology Voltage independent
    [Ics] rated service breaking capacity 6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
    Rated breaking and making capacity Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
    Limitation class 3 conforming to EN/IEC 61009-2-1
    [Ui] rated insulation voltage 400 V AC 50 Hz
    [Uimp] rated impulse withstand voltage 4 kV
    Contact position indicator Yes
    Control type Toggle
    Local signalling ON, OFF, fault trip
    Mounting mode Clip-on
    Mounting support DIN rail
    Comb busbar and distribution block compatibility Top or bottom: YES
    Connection pitch 9 mm between phase and neutral
    9 mm pitches 4
    Height 85 mm
    Width 36 mm
    Depth 73 mm
    Net weight 125 g
    Colour White
    Mechanical durability 20000 cycles
    Electrical durability 20000 cycles
    Locking options description Padlocking device
    Connections - terminals Single terminal top or bottom 1…16 mm² rigid
    Single terminal top or bottom 1…10 mm² flexible
    Single terminal top or bottom 1…10 mm² flexible with ferrule
    Wire stripping length 15 mm for top or bottom connection
    Tightening torque 2 N.m top or bottom
    Earth-leakage protection Integrated
  • Environment and Packing Units

    Environment
    Standards EN/IEC 61009-2-1
    Product certifications VDE
    GOST
    IP degree of protection IP20 conforming to IEC 60529
    IP40 (modular enclosure) conforming to IEC 60529
    Pollution degree 3
    Overvoltage category III conforming to IEC 60364
    Electromagnetic compatibility 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1
    Tropicalisation 2 conforming to IEC 60068-1
    Relative humidity 95 % at 55 °C
    Ambient air temperature for operation -5…60 °C
    Ambient air temperature for storage -40…85 °C
    Packing Units
    Unit Type of Package 1 PCE
    Number of Units in Package 1 1
    Package 1 Height 4.0 cm
    Package 1 Width 8.5 cm
    Package 1 Length 10.0 cm
    Package 1 Weight 208.0 g
    Unit Type of Package 2 S03
    Number of Units in Package 2 54
    Package 2 Height 30.0 cm
    Package 2 Width 30.0 cm
    Package 2 Length 40.0 cm
    Package 2 Weight 12.352 kg
No Reviews YetShare your thoughts. Be the first to leave a review.
bottom of page