top of page
C16F3TM125

C16F3TM125

SKU: TR
$293.80Price

C16F3TM125 - SCHNEIDER

Circuit breaker ComPacT NSX160F, 36kA at 415VAC, TMD trip unit 125A, 3 poles 3d

In Stock

Description

This ComPacT NSX160F is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 125A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX160F is part of Schneider Electric EcoStruxure Power architecture.

Read Less

 

  • Specifications

    Range ComPacT new generation
    Product name ComPacT NSX new generation
    Device short name NSX160F
    product or component type Circuit breaker
    Device application Distribution
    Poles description 3P
    Protected poles description 3D
    [In] rated current 125 A at 40 °C
    [Ue] rated operational voltage 690 V AC 50/60 Hz
    Network type AC
    Network frequency 50/60 Hz
    Suitability for isolation Yes conforming to EN/IEC 60947-2
    Utilisation category Category A
    [Icu] rated ultimate short-circuit breaking capacity 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
    22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
    8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    35 kA at 480 V AC 50/60 Hz conforming to UL 508
    Performance level F 36 kA 415 V AC
    Trip unit name TM-D
    Trip unit technology Thermal-magnetic
    Trip unit protection functions LI
    Control type Toggle
    Circuit breaker mounting mode Fixed
  • Complementary

    [Ui] rated insulation voltage 800 V AC 50/60 Hz
    [Uimp] rated impulse withstand voltage 8 kV
    [Ics] rated service short-circuit breaking capacity 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
    22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
    8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    Mechanical durability 40000 cycles
    Electrical durability 40000 cycles at 440 V In/2
    20000 cycles at 440 V In
    15000 cycles at 690 V In/2
    7500 cycles at 690 V In
    Mounting support Backplate
    Mounting position Horizontal and vertical
    Flat on the back
    Upside connection Front
    downside connection Front
    Connection pitch 35 mm
    Protection type L : for overload protection (thermal)
    I : for short-circuit protection (magnetic)
    Trip unit rating 125 A at 40 °C
    Long-time pick-up adjustment type Ir (thermal protection) Adjustable
    [Ir] long-time protection pick-up adjustment range 0.7...1 x In
    Long-time protection delay adjustment type tr Fixed
    [tr] long-time protection delay adjustment range 120…400 s at 1.5 x In
    15 s at 6 x Ir
    Instantaneous protection pick-up adjustment type Ii Fixed
    [Ii] instantaneous protection pick-up adjustment range 1250 A
    earth-leakage protection Without
    Number of slots for electrical auxiliaries 5 slot(s)
    Width (W) 105 mm
    Height (H) 161 mm
    Depth (D) 86 mm
    net weight 2.2 kg
  • Environmental

    Standards EN/IEC 60947
    Product certifications CCC
    EAC
    Marine
    Overvoltage category Class II
    Electrical shock protection class Class II
    Pollution degree 3 conforming to IEC 60664-1
    IP degree of protection IP40 conforming to IEC 60529
    IK degree of protection IK07 conforming to IEC 62262
    Ambient air temperature for operation -25…70 °C
    ambient air temperature for storage -50…85 °C
    Relative humidity 0…95 %
    Operating altitude 0...2000 m without derating
    2000 m...5000 m with derating
No Reviews YetShare your thoughts. Be the first to leave a review.