C16L3
C16L3 - SCHNEIDER
Circuit breaker basic frame, ComPacT NSX160L, 150kA/415VAC, 3 poles, 160A frame rating, without trip unit
In Stock
Description
This basic frame comes without a trip unit and is compatible with any trip unit that must be ordered separately Breaking capacity Icu 70kA / 415VAC 50/60Hz Operating voltage 690VAC 50/60Hz (limited to 440VAC 50/60Hz if earth leakage protection is available) Various optional functions and accessories Dimensions 140mm x 161mm x 86mm Complies with International Standards (IEC 60947), CCC, EAC and marine specifications ComPacT NSX160H is part of Schneider Electric EcoStruxure Power architecture.
Specifications
Range ComPacT new generation Product name ComPacT NSX new generation Device short name NSX160L product or component type Basic frame Device application Distribution Poles description 3P [In] rated current 160 A at 40 °C [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 Network type AC Network frequency 50/60 Hz Suitability for isolation Yes conforming to EN/IEC 60947-2 Utilisation category Category A [Icu] rated ultimate short-circuit breaking capacity 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2Performance level L 150 kA 415 V AC Control type Toggle Mounting mode Fixed Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2 [Ics] rated service short-circuit breaking capacity 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
70 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2Mechanical durability 40000 cycles conforming to IEC 60947-2 Electrical durability 40000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
15000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
20000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
7500 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2Mounting support Backplate Upside connection Front downside connection Front Connection pitch 35 mm Protection type Without protection Width (W) 105 mm Height (H) 161 mm Depth (D) 86 mm Environmental
Standards EN/IEC 60947-2
UL 508Product certifications CSA
ULPollution degree 3 conforming to IEC 60664-1 IP degree of protection IP40 conforming to IEC 60529 IK degree of protection IK07 conforming to IEC 62262 Ambient air temperature for operation -25…70 °C ambient air temperature for storage -50…85 °C