C25F3TM200
C25F3TM200 - SCHNEIDER
Circuit breaker, ComPacT NSX250F, 36kA/415VAC, 3 poles, TMD trip unit 200A
IN STOCK
Description
This ComPacT NSX250F is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 200A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX250F is part of Schneider Electric EcoStruxure Power architecture.
Specifications
Main Range ComPacT new generation Product name ComPacT NSX new generation Device short name NSX250F product or component type Circuit breaker Device application Distribution poles description 3P Protected poles description 3D [In] rated current 200 A at 40 °C [Ue] rated operational voltage 690 V AC 50/60 Hz Network type AC Network frequency 50/60 Hz Suitability for isolation Yes conforming to EN/IEC 60947-2 Utilisation category Category A [Icu] rated ultimate short-circuit breaking capacity 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 480 V AC 50/60 Hz conforming to UL 508
15 kA at 600 V AC 50/60 Hz conforming to UL 508Performance level F 36 kA 415 V AC Trip unit name TM-D Trip unit technology Thermal-magnetic Trip unit protection functions LI Control type Toggle Circuit breaker mounting mode Fixed Complementary [Ui] rated insulation voltage 800 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 8 kV [Ics] rated service short-circuit breaking capacity 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2Mechanical durability 20000 cycles Electrical durability 20000 cycles at 440 V In/2
10000 cycles at 440 V In
10000 cycles at 690 V In/2
5000 cycles at 690 V Inmounting support Backplate Mounting position Horizontal and vertical
Flat on the backUpside connection Front downside connection Front Connection pitch 35 mm Protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)Trip unit rating 200 A at 40 °C Long-time pick-up adjustment type Ir (thermal protection) Adjustable [Ir] long-time protection pick-up adjustment range 0.7...1 x In Long-time protection delay adjustment type tr Fixed [tr] long-time protection delay adjustment range 120…400 s at 1.5 x In
15 s at 6 x IrInstantaneous protection pick-up adjustment type Ii Adjustable [Ii] instantaneous protection pick-up adjustment range 5...10 x In Earth-leakage protection Without Number of slots for electrical auxiliaries 5 slot(s) Width (W) 105 mm Height (H) 161 mm Depth (D) 86 mm net weight 2.4 kg Environment Standards EN/IEC 60947 Product certifications Marine
CCC
EACOvervoltage category Class II Electrical shock protection class Class II Pollution degree 3 conforming to IEC 60664-1 IP degree of protection IP40 conforming to IEC 60529 IK degree of protection IK07 conforming to IEC 62262 Ambient air temperature for operation -25…70 °C ambient air temperature for storage -50…85 °C Relative humidity 0…95 % Operating altitude 0...2000 m without derating
2000 m...5000 m with derating