top of page
C63F3

C63F3

SKU: TR
$834.60Price

C63F3 - SCHNEIDER

Circuit breaker basic frame, ComPacT NSX630F, 36kA at 415VAC 50/60 Hz, 630A, without trip unit, 3 poles

IN STOCK

Description

This is a 3 poles basic frame for ComPacT NSX630F. ComPacT NSX is designed to optimize space and breaking capacity for all standard and specific applications. This basic frame comes without trip unit, and is compatible with any type of trip unit which has to be ordered separately The breaking capacity Icu is 36kA at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz (limited to 440VAC 50/60Hz if there is an earth-leakage protection). It can be equipped with a variety of optional functions and accessories. The dimensions are 140mm x 255mm x 110mm. It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX630F is part of Schneider Electric EcoStruxure Power architecture.

  • Specifications

    Main
    Range ComPacT new generation
    Product name ComPacT NSX new generation
    Device short name NSX630F
    product or component type Basic frame
    Device application Distribution
    poles description 3P
    [In] rated current 630 A at 40 °C
    [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
    Network type AC
    Network frequency 50/60 Hz
    Suitability for isolation Yes conforming to EN/IEC 60947-2
    Utilisation category Category A
    [Icu] rated ultimate short-circuit breaking capacity 85 kA at 240 V AC 50/60 Hz conforming to UL 508
    25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
    36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    35 kA at 480 V AC 50/60 Hz conforming to UL 508
    20 kA at 600 V AC 50/60 Hz conforming to UL 508
    20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
    30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    Performance level F 36 kA 415 V AC
    Control type Toggle
    mounting mode Fixed
    Complementary
    [Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
    [Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
    [Ics] rated service short-circuit breaking capacity 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
    25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
    30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    Mechanical durability 15000 cycles conforming to IEC 60947-2
    Electrical durability 6000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
    2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
    4000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
    8000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
    mounting support Backplate
    Upside connection Front
    downside connection Front
    Connection pitch 45 mm
    Protection type Without protection
    Width (W) 140 mm
    Height (H) 255 mm
    Depth (D) 110 mm
    Environment
    Standards EN/IEC 60947-2
    UL 508
    Product certifications UL
    CSA
    Pollution degree 3 conforming to IEC 60664-1
    IP degree of protection IP40 conforming to IEC 60529
    IK degree of protection IK07 conforming to IEC 62262
    Ambient air temperature for operation -25…70 °C
    ambient air temperature for storage -50…85 °C
No Reviews YetShare your thoughts. Be the first to leave a review.
bottom of page