top of page
CAE22M5

CAE22M5

SKU: TR
$9.00Price

CAE22M5 - SCHNEIDER

Easy TeSys control relay - 2 NO + 2 NC <= 690 V - 220 VAC

In Stock

Description

EasyPact TVS control relay for utilization categories AC-15/AC-14 up to 10A/690V. It provides 4 instantaneous contacts (2NO+2NC), a 220V 50Hz AC coil, connections by screw clamp terminals. For demanding applications with standard operating rates until 3 cycles/second, it procures standard reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach).

  • Specifications

    Range Easy TeSys
    Range of product Easy TeSys Control Relay
    product or component type Control relay
    Device short name CAE
    contactor application Control circuit
    Colour Grey (RAL 7011)
  • Complementary

    Utilisation category AC-14
    AC-15
    Pole contact composition 2 NO + 2 NC
    [Ue] rated operational voltage <= 690 V AC
    Control circuit type AC at 50 Hz
    [Uc] control circuit voltage 220 V AC 50 Hz
    [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
    [Ith] conventional free air thermal current 10 A (at 40 °C)
    Irms rated making capacity 140 A at 690 V AC conforming to IEC 60947-5-1
    [Icw] rated short-time withstand current 120 A - 500 ms
    140 A - 100 ms
    Associated fuse rating 10 A gG at 690 V conforming to IEC 60947-5-1
    [Ui] rated insulation voltage 690 V conforming to IEC 60947-5-1
    Mounting support Rail
    Plate
    Connections - terminals Screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end
    Screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end
    Screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
    Screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
    Screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end
    Screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end
    Recommended tightening torque 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
    Control circuit voltage limits Operational: 0.85...1.1 Uc at 50 Hz
    Drop-out: 0.3...0.6 Uc
    Operating time 4...19 ms coil energisation and NC opening
    12...22 ms coil energisation and NO closing
    4...12 ms coil de-energisation and NC opening
    6...17 ms coil de-energisation and NO closing
    Mechanical durability 10 Mcycles
    Maximum operating rate 180 cyc/mn
    Inrush power in VA 70 VA 50 Hz (at 20 °C)
    Hold-in power consumption in VA 8 VA 50 Hz (at 20 °C)
    Minimum switching voltage 17 V
    Minimum switching current 5 mA
    Non-overlap time 1.5 ms on energisation between NC and NO contact
    1.5 ms on de-energisation between NC and NO contact
    Insulation resistance > 10 MOhm
    Mechanical robustness Shocks control relay open: 7 Gn for 11 ms
    Shocks control relay closed: 10 Gn for 11 ms
    Vibrations control relay open: 1.5 Gn, 5...300 Hz
    Vibrations control relay closed: 3 Gn, 5...300 Hz
    Height 74 mm
    Width 45 mm
    Depth 80 mm
    net weight 0.28 kg
  • Environmental

    Standards IEC 60947-5-1
    Product certifications GOST
    IP degree of protection IP2X conforming to IEC 60529
    Protective treatment TH conforming to IEC 60068
    Ambient air temperature for operation -20…70 °C
    ambient air temperature for storage -60…80 °C
    Operating altitude 3000 m without derating
No Reviews YetShare your thoughts. Be the first to leave a review.