G12F3F100
G12F3F100 - SCHNEIDER
GoPact Switch 125F 30kA AC 3P3D 100A Fixed
IN STOCK
Description
GoPact MCCB has a good price-performance ratio for basic applications and provides reliable electrical protection for your applications Breaking capacity (Icu) is 30kA rms at 415VAC 50/60Hz operating voltage 415VAC 50/60Hz This product has a 100A rating (In) There is a thermal-magnetic trip unit (TMD). This TMD trip unit has a fixed thermal protection Ir (against overloads) setting 1xIn (100A) a fixed magnetic (against short circuits) protection setting 10xIn (1000A) GoPact MCCB, which is simple to select and install. comes with optional accessories Product dimensions 75mm (width) x 130mm (Height) x 60mm (depth) Weight 0.7 kg GoPact MCCB 125 is IEC 60947-1 and IEC 60947-2 certified The GoPact MCCB series benefits from Schneider Electric quality assurance.
Specifications
Product series GoPact MCCB Product or component type Circuit breaker Name of the product GoPact MCCB 125 device application Distribution pole definition 3P protected pole description 3d [In] rated current 100 A at 40 °C [Ue] nominal operating voltage 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 suitability for insulation Yes conforming to EN/IEC 60947-2 usage category Category A [Icu] rated ultimate short-circuit breaking capacity 30 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2Performance level F 30 kA 380/415 V AC Trip Unit Name TM-D trip unit technology Thermal Magnetic Trip Unit Protection Functions LI Control type Transition Circuit breaker mounting mode Still Complement
[Ui] nominal insulation voltage 440 V AC conforming to EN/IEC 60947-2 [Uimp] nominal impulse withstand voltage 6 kV conforming to EN/IEC 60947-2 [Ics] rated service short-circuit breaking capacity 15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2Mechanical durability 30000 cycles electrical durability 8000 cycles at 415 V In power dissipation per pole 18.7W mounting support Back plate mounting position Horizontal and vertical
Flat on backtop link Front downlink Front Connection terminals Screw terminals connection range 25mm protection type L : for overload protection (thermal)
I : for short circuit protection (magnetic)tripping unit degree 100 A at 40 °C Long-time pick-up adjustment type Ir (thermal protection) Still [Ir] long-time protection pick-up adjustment range 1 x In Long-time protection delay adjustment type tr Still Instantaneous protection pick-up adjustment type Ii Still [ii] instantaneous protection pick-up adjustment range 10 x In Width (W) 75mm Height (H) 130mm Depth(D) 60mm Product weight 0.7kg colour Gray (RAL 7035) Environment
standards EN/IEC 60947-1
EN/IEC 60947-2
EN/IEC 60947-2 Annex Hovervoltage category III degree of pollution 3 conforming to IEC 60664-1 IP protection degree IP20 conforming to IEC 60529 ambient air temperature for operation -20…55 °C Storage environmental conditions -35…85 °C working height 0...2000 m without derating
2000...5000 m with derating