GV2ME14
SKU: TR
$25.23Price
GV2ME14 - SCHNEIDER
Motor circuit breaker, TeSys GV2, 3P, 6-10 A, thermal magnetic, screw clamp terminals
In Stock
Description
TeSys GV motor circuit breaker, 3 poles (3P), 10A/690V, for 3-phase motor applications 3-4kW@400V. It provides a thermal-magnetic protection with a thermal setting range 6-10A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Specifications
Range TeSys Deca Product name TeSys GV2
TeSys Decaproduct or component type Motor circuit breaker Device short name GV2ME Device application Motor protection Trip unit technology Thermal-magnetic Complementary
Poles description 3P Network type AC Utilisation category Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
AC-3e conforming to IEC 60947-4-1Network frequency 50/60 Hz conforming to IEC 60947-4-1 Fixing mode 35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)Motor power kW 3 kW at 400/415 V AC 50/60 Hz
4 kW at 400/415 V AC 50/60 Hz
4 kW at 500 V AC 50/60 Hz
5.5 kW at 500 V AC 50/60 Hz
5.5 kW at 690 V AC 50/60 Hz
7.5 kW at 690 V AC 50/60 HzBreaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service short-circuit breaking capacity 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2Environmental
Standards EN/IEC 60947-2
EN/IEC 60947-4-1Product certifications CCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCAIK degree of protection IK04 IP degree of protection IP20 conforming to IEC 60529 Climatic withstand Conforming to IACS E10 ambient air temperature for storage -40…80 °C Fire resistance 960 °C conforming to IEC 60695-2-11 Ambient air temperature for operation -20…60 °C Mechanical robustness Shocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 HzOperating altitude 2000 m
No Reviews YetShare your thoughts.