TeSys GV motor circuit breaker, 3 poles (3P), 40A/690V, for 3-phase motor applications 18.5kW@400V. It provides a thermal-magnetic protection with a thermal setting range 30-40A, magnetic tripping at 14xIn, high breaking capacity Icu 50kA@400V. Connection by Everlink BTR screw terminals. Start-stop control by rotary knob guaranteed for 50 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Specifications Main
Main Range TeSys Deca Product name TeSys GV3
TeSys Decaproduct or component type Motor circuit breaker Device short name GV3P Device application Motor protection Trip unit technology Thermal-magnetic Complementary Poles description 3P Network type AC Utilisation category AC-3 conforming to IEC 60947-4-1 Network frequency 50/60 Hz conforming to IEC 60947-4-1 Fixing mode 35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws)Motor power kW 18.5 kW at 400/415 V AC 50/60 Hz
22 kW at 500 V AC 50/60 Hz
37 kW at 690 V AC 50/60 HzBreaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service short-circuit breaking capacity 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2Control type Rotary handle [In] rated current 40 A Thermal protection adjustment range 30…40 A conforming to IEC 60947-4-1 Magnetic tripping current 560 A [Ith] conventional free air thermal current 40 A conforming to IEC 60947-4-1 [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2 Phase failure sensitivity Yes conforming to IEC 60947-4-1 Suitability for isolation Yes conforming to IEC 60947-1 Power dissipation per pole 8 W Mechanical durability 50000 cycles Electrical durability 50000 cycles for AC-3 at 415 V In Rated duty Continuous conforming to IEC 60947-4-1 Tightening torque 5 N.m - on screw clamp terminal Width 55 mm Height 132 mm Depth 136 mm net weight 0.96 kg Colour Dark grey Environment
Environment Standards EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1Product certifications CCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
ABS
DNV-GL
UKCAIK degree of protection IK09 enclosure IP degree of protection IP20 conforming to IEC 60529 Climatic withstand Conforming to IACS E10 ambient air temperature for storage -40…80 °C Fire resistance 960 °C conforming to IEC 60695-2-11 Ambient air temperature for operation -20…60 °C Mechanical robustness Shocks: 15 Gn for 11 ms contactor open
Shocks: 30 Gn for 11 ms contactor closed
Vibrations: 4 Gn, 5...300 HzOperating altitude 3000 m Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 16.000 cm Package 1 Width 6.500 cm Package 1 Length 14.600 cm Package 1 Weight 983.000 g Unit Type of Package 2 P06 Number of Units in Package 2 120 Package 2 Height 75.000 cm Package 2 Width 60.000 cm Package 2 Length 80.000 cm Package 2 Weight 133.960 kg Contractual warranty Warranty 18 months properties