LUCD32FU - SCHNEIDER

Advanced control unit, TeSys Ultra, 8A to 32A, 3P motors, protection & diagnostic, class 20, coil 110-240VAC/DC

IN STOCK

Description

TeSys U control and diagnostic unit to be inserted in advanced power bases LUB320, LUB380 to form a TeSys U starter controller, for 3-phase motor applications up to 15kW@400V. It provides full protection to motors with a rated current Ir 8-32A (Ir adjustable), overload tripping class 20, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). It provides a thermal overload alarm to be used locally using a LUFDA module or remotely using a LULC module, and a test push button for overload simulation. To be used with a 110-240V AC / 110-220V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

 

 

  • Specifications

    Main
    Range TeSys
    Range of Product TeSys Ultra
    Product name TeSys Ultra
    Device short name LUCD
    Product or Component Type Advanced control unit
    Device Application Motor control
    Motor protection
    Product Specific Application Basic protection and advanced functions, communication
    main function available Protection against overload and short-circuit
    Manual reset
    Protection against phase failure and phase imbalance
    Earth fault protection
    Product compatibility Power base LUB32
    Power base LUB38
    Power base LUB320
    Power base LUB380
    Reversing contactor breaker LU2B32FU
    Reversing contactor breaker LU2B38FU
    [Ue] rated operational voltage 690 V AC
    Network frequency 40...60 Hz
    Load type 3-phase motor self-cooled
    Utilisation category AC-44
    AC-41
    AC-43
    Motor power kW 15 kW 400...440 V AC 50/60 Hz
    15 kW 500 V AC 50/60 Hz
    18.5 kW 690 V AC 50/60 Hz
    rated motor current adjustment range 8…32 A
    Thermal overload class Class 20 40…60 Hz -13…158 °F (-25…70 °C) IEC 60947-6-2
    Class 20 40…60 Hz -13…158 °F (-25…70 °C) UL 508
    Tripping threshold 14.2 x Ir +/- 20 %
    Phase failure sensitivity Yes
    [Uc] control circuit voltage 110...240 V AC
    110...220 V DC
    Complementary
    Control circuit voltage limits 88...264 V AC 110...240 V in operation
    88...242 V DC 110...220 V in operation
    55 V AC 110...240 V drop-out
    55 V DC 110...220 V drop-out
    Typical current consumption 280 mA 110...240 V AC I maximum while closing with LUB32
    280 mA 110...240 V AC I maximum while closing with LUB38
    280 mA 110...220 V DC I maximum while closing with LUB32
    280 mA 110...220 V DC I maximum while closing with LUB38
    25 mA 110...240 V AC I rms sealed with LUB32
    25 mA 110...240 V AC I rms sealed with LUB38
    25 mA 110...220 V DC I rms sealed with LUB32
    25 mA 110...220 V DC I rms sealed with LUB38
    Heat dissipation 3 W control circuit with LUB32
    3 W control circuit with LUB38
    Operating time 35 ms opening with LUB32 control circuit
    35 ms opening with LUB38 control circuit
    50 ms closing with LUB32 control circuit
    50 ms closing with LUB38 control circuit
    Reset Manual reset
    Standards EN 60947-6-2
    IEC 60947-6-2
    UL 60947-4-1, with phase barrier
    CSA C22.2 No 60947-4-1, with phase barrier
    Product Certifications CE
    UL
    CSA
    CCC
    EAC
    ASEFA
    ATEX
    Marine
    [Ui] rated insulation voltage 690 V IEC 60947-6-2
    600 V UL 60947-4-1
    600 V CSA C22.2 No 60947-4-1
    [Uimp] rated impulse withstand voltage 6 kV IEC 60947-6-2
    Safe separation of circuit 400 V SELV between the control and auxiliary circuits IEC 60947-1
    400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
    Fixing mode Plug-in (front face)
    Width 1.77 in (45 mm)
    Height 2.60 in (66 mm)
    Depth 2.36 in (60 mm)
    Compatibility code LUCD
    Environment
    IP degree of protection IP20 front panel and wired terminals IEC 60947-1
    IP20 other faces IEC 60947-1
    IP40 front panel outside connection zone IEC 60947-1
    Protective treatment TH IEC 60068
    Ambient air temperature for operation -13…158 °F (-25…70 °C)
    Ambient Air Temperature for Storage -40…185 °F (-40…85 °C)
    Operating altitude 6561.68 ft (2000 m)
    Fire resistance 1760 °F (960 °C) parts supporting live components IEC 60695-2-12
    1202 °F (650 °C) IEC 60695-2-12
    Shock resistance 10 gn power poles open IEC 60068-2-27
    15 gn power poles closed IEC 60068-2-27
    Vibration resistance 2 gn 5…300 Hz power poles open IEC 60068-2-6
    4 gn 5…300 Hz power poles closed IEC 60068-2-6
    Resistance to electrostatic discharge 8 kV 3 in open air IEC 61000-4-2
    8 kV 4 on contact IEC 61000-4-2
    Non-dissipating shock wave 1 kV serial mode IEC 60947-6-2
    2 kV common mode IEC 60947-6-2
    Resistance to radiated fields 9.14 V/m (10 V/m) 3 IEC 61000-4-3
    Resistance to fast transients 2 kV 3 serial link IEC 61000-4-4
    4 kV 4 all circuits except for serial link IEC 61000-4-4
    Immunity to radioelectric fields 10 V IEC 61000-4-6
    Immunity to microbreaks 3 ms
    Immunity to voltage dips 70 % / 500 ms IEC 61000-4-11
    Ordering and shipping details
    Category US10I1122397
    Discount Schedule 0I11
    GTIN 3389110365078
    Returnability Yes
    Country of origin FR