top of page
RM35TF30

RM35TF30

SKU: TR
$136.43Price

RM35TF30 - SCHNEIDER

multifunction phase control relay RM35-T - range 194..528 V AC

In Stock

Description

This Harmony RM35-T multi function control relay allows monitoring of power supply circuits in 3-phase networks. This modular multi function 3-phase control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a selectable memory function, integral LED for indicating control status, sealable cover, with simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. Multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC.

 

Quantity
  • Specifications

    Range of product Harmony Control Relays
    Relay type Multifunction control relay
    product or component type 3-phase control relay
    Product specific application For 3-phase supply
    Relay name RM35TF
    Relay monitored parameters Undervoltage and overvoltage in window mode
    Phase sequence
    Phase failure detection
    Asymmetry
    time delay Adjustable 0.1...10 s, +/- 10 % of the full scale value Tt- time delay upon fault
    Switching capacity in VA 1250 VA
    Measurement range 220...480 V AC
    Contacts type and composition 2 C/O
    [Uc] control circuit voltage 220...480 V
  • Complementary

    Reset time 1500 ms at 480 V
    Maximum switching voltage 250 V AC
    250 V DC
    Minimum switching current 10 mA at 5 V DC
    Maximum switching current 5 A AC
    5 A DC
    [Un] rated nominal voltage , self-powered
    Supply voltage limits 194…528 V AC, 3 phases
    Control circuit voltage limits - 12 % + 10 % And
    Power consumption in VA 0…22 VA at 400 V AC 50 Hz
    Voltage detection threshold < 194V
    control circuit frequency 50...60 Hz +/- 10 %
    Output contacts 2 C/O
    Nominal output current 5 A
    Measurement voltage limits 176…528 V AC
    Hysteresis 2 %
    delay at power up 650 ms
    Maximum measuring cycle 140 ms measurement cycle as true rms value
    Threshold adjustment voltage 2...20 % of Un selected
    -12...-2 % in the range 220 V AC
    +2...+10 % in the range 480 V AC
    Voltage range 220...480 V phase to phase
    Adjustment of asymmetry threshold 5...15 % of Un selected
    Repeat accuracy 0.3 % for time delay
    0.5 % for input and measurement circuit
    Measurement error < 1 % over the whole range with voltage variation
    0.05 %/°C with temperature variation
    Response time < 200 ms (in the event of a fault)
    marking THIS
    Overvoltage category III conforming to IEC 60664-1
    Insulation resistance > 500 MOhm at 500 V DC conforming to IEC 60255-5
    > 500 MOhm at 500 V DC conforming to IEC 60664-1
    [Ui] rated insulation voltage 400 V conforming to IEC 60664-1
    Supply frequency 50/60 Hz +/- 10 %
    Operating position Any position without derating
    Connections - terminals Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
    Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
    Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
    Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
    Tightening torque 0.6…1 N.m conforming to IEC 60947-1
    Housing material Self-extinguishing plastic
    Local signalling LED (green) for power ON
    LED (yellow) for relay ON
    LED (yellow) for fault
    Mounting support 35 mm symmetrical DIN rail conforming to IEC 60715
    Electrical durability 100000 cycles
    Mechanical durability 30000000 cycles
    Operating rate <= 360 operations/hour full load
    Utilisation category AC-12 conforming to IEC 60947-5-1
    AC-13 conforming to IEC 60947-5-1
    AC-14 conforming to IEC 60947-5-1
    AC-15 conforming to IEC 60947-5-1
    DC-12 conforming to IEC 60947-5-1
    DC-13 conforming to IEC 60947-5-1
    Safety reliability data MTTFd = 399.5 years
    B10d = 360000
    Width 35 mm
    net weight 0.13 kg
    Control type Without test button
  • Environmental

    Electromagnetic compatibility Emission standard for industrial environments conforming to IEC 61000-6-4
    Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
    Immunity for industrial environments conforming to IEC 61000-6-2
    Standards IEC 60255-1
    Product certifications GL
    UL
    CSA
    GOST
    C-Tick
    Directives 89/336/EEC - electromagnetic compatibility
    73/23/EEC - low voltage directive
    ambient air temperature for storage -40…70 °C
    Ambient air temperature for operation -20…50 °C
    Relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
    Vibration resistance 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6
    1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
    Shock resistance 15 gn for 11 ms conforming to IEC 60255-21-1
    IP degree of protection IP20 (terminals) conforming to IEC 60529
    IP30 (casing) conforming to IEC 60529
    Pollution degree 3 conforming to IEC 60664-1
    Dielectric test voltage 2 kV, 1 min AC 50 Hz
    Non-dissipating shock wave 4 kV