VarPlus logic is a simple and efficient Power Controller for a automatic power factor correction equipment to maintain the power factor. It is a simple and intelligent relay which measures,monitor and Controls the reactive energy. It comes with Easy Commisioning , Step Size detection and monitoring along with the variour alarms. VPL12 can be used for 12 steps in a PFC equippment.
GTIN/UPC/EAN: 3606480800115
Specifications Main
Main Range PowerLogic Product name PowerLogic PFC Controller Device short name VPL12 product or component type Power factor controller Complementary Number of step output contacts 12 [Us] rated supply voltage 90...550 V AC
<= 999 kV AC with external VTMeasurement current 0…5 A Measurement voltage 90…550 V AC 50/60 Hz Operating mode Manual or automatic Number of quadrant operation for generator application 4 Device connection Communication protocol: Modbus interface: RS485 Input function Switch: 1 x dry contact Colour code Front: dark grey RAL 7016 Display type Backlit LCD display size 56 x 25 mm Function available Manual programming
Automatic initialisation
Automatic detection
Advanced programming (expert)
Any step sequenceMetering type Power factor and displacement PF (signed, four quadrant)
Total current harmonic distortion THD (I)
Power factor average over lifetime
Temperature maximum
Phase current I1, I2, I3 RMS on load
Active power P, P1, P2, P3 on load
Reactive power Q, Q1, Q2, Q3 on load
Apparent power S, S1, S2, S3 on load
Voltage U21, U32, U13, V1, V2, V3 on loadtype of measurement Capacitor current overload Irms/I1
Individual voltage harmonic
Power factor
Operating time
Cos φ
Ambient temperature inside the cubicle
Tan φInformation displayed Number of switching cycles per step
Individual step size in kVAr
Remaining step capacity in %Type of alarms Step power loss (< 75 %) / Action: message and alarm contact + step blocked
Step faulty / Action: message and alarm contact + step blocked
High current (> 6 A CT) / Action: message and alarm contact
Hunting (unstable regulation) / Action: message and alarm contact + step blocked
Low current (< 15 mA CT) / Action: message and alarm contact
Overcompensation / Action: message and alarm contact
Capacitor current overload (Irms/I1) (> 130 % I1) / Action: message and alarm contact + step switched off
Overtemperature (50 °C) / Action: message and alarm contact + step switched off
Overtemperature (30 °C) / Action: fan switch
Overvoltage (+/- 10 %) / Action: message and alarm contact + control stopped
Total harmonic distortion (> 7 %) / Action: message and alarm contact + step switched offData recording 5 alarms Operational Hours alarm 100000 h without maintenance Operational counter alarm 65000 cycles without maintenance Input type Phase to phase
Phase to neutral
Insensitive to CT polarity
Insensitive to phase rotation polarity
Current input CT...X/5 A and X/1 AOutput type Control relay: 0.2 A 110 V DC
Control relay: 1 A 48 V DC
Control relay: 2 A 400 V AC 50/60 Hz
Control relay: 1 A 24 V DC
Control relay: 5 A 250 V AC 50/60 Hz
Control relay: 5 A 120 V AC 50/60 Hz
Fan: 5 A 250 V AC 50/60 Hz
Fan: 1 A 48 V DC
Alarm relay: 5 A 250 V AC 50/60 Hz
Alarm relay: 1 A 48 V DCMaximum at the common terminal 10 A Settings operating mode Automatic
ManualType of setting Choice of stepping programs: auto
Choice of stepping programs: LIFO
Choice of stepping programs: linear
Delay between 2 successive switch on the same step: 5...1200 s
Step configuration programming: auto
Step configuration programming: off
Step configuration programming: fixed
Target cos phi: 0.7 inductive...0.7 capacitive
Target cos phi: dual cos φMeasurement accuracy Voltage +/- 1 %
Current +/- 1 %
Frequency +/- 1 %
Energy (P,Q,S) +/- 2 %
Cos φ +/- 2 %
Total voltage harmonic distortion THD (U) +/- 2 %
Individual voltage harmonic +/- 3 %
Temperature +/- 3 °CTime delay range 1...6500 s (on reconnection)
1...6500 s (on response)Provided equipment User manual Mounting mode Flush-mounted Mounting support Panel - thickness: 1…3 mm Mounting location In cabinet Cut-out dimensions 138 x 138 mm Height 144 mm Width 144 mm Depth 58 mm net weight 0.6 kg Additional Information
Environment Standards IEC 61000-6-4
UL 61010-1
EN 61010-1
IEC 61000-6-2
IEC 61326-1Product certifications EAC
NRTL
cNRTL
CEIP degree of protection Front face: IP41
Rear face: IP20Operating altitude <= 2000 m Ambient air temperature for operation -20…60 °C ambient air temperature for storage -40…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 9.200 cm Package 1 Width 17.700 cm Package 1 Length 18.400 cm Package 1 Weight 724.000 g Unit Type of Package 2 S03 Number of Units in Package 2 8 Package 2 Height 30.000 cm Package 2 Width 30.000 cm Package 2 Length 40.000 cm Package 2 Weight 6.155 kg Unit Type of Package 3 P06 Number of Units in Package 3 64 Package 3 Height 75.000 cm Package 3 Width 60.000 cm Package 3 Length 80.000 cm Package 3 Weight 58.408 kg properties
Power Controller for an automatic power factor correction equipment to maintain the power factor
notification_ok
Simple and efficient with ready to connect with RS485 modbus communication
notification_ok
Best in class performance, safety and reliability